Chapter 14 Fault Codes and Descriptions
CFP2000
14-20
ID*
Display on LCD Keypad
Fault Name
Fault Descriptions
26
Over torque 1
(ot1)
When output current exceeds the over-torque detection
level (Pr.06-07) and exceeds over-torque detection time
(Pr.06-08), and when Pr.06-06 or Pr.06-09 is set to 2 or
4, the ot1 error displays.
Action and Reset
Action level
Pr.06-07
Action time
Pr.06-08
Fault treatment parameter
Pr.06-06
0: No function
1: Continue operation after Over-torque detection during constant speed
operation
2: Stop after Over-torque detection during constant speed operation
3: Continue operation after Over-torque detection during RUN
4: Stop after Over-torque detection during RUN
Reset method
Reset condition
Auto When Pr.06-06=1 or 3, ot1 is a “Warning”. The warning is
automatically cleared when the output current < (Pr.06-07 – 5%)
Manual When Pr.06-06=2 or 4, ot1 is a “Fault”. You must reset manually.
Record
Immediately reset
Active level
When Pr.06-06=2 or 4, ot1 is a “Fault”, and the fault is recorded.
Cause
Corrective Actions
Incorrect parameter setting
Reset Pr.06-07 and Pr.06-08
Mechanical failure (e.g.
over-torque, mechanical lock)
Remove the causes of malfunction.
The load is too large
Reduce the load.
Replace the motor with a larger capacity model.
Accel./Decel. time and working
cycle are too short
Increase the setting values for Pr.01-12–Pr.01-19 (accel./decel. time)
V/F voltage is too high
Adjust settings for Pr.01-01–01-08 (V/F curve), especially the setting value for
the mid-point voltage (if the mid-point voltage is set too low, the load capacity
decreases at low speed).
The motor capacity is too small
Replace the motor with a larger capacity model.
Overload during low-speed
operation
Decrease low-speed operation time.
Increase the motor capacity.
Torque compensation is too large Adjust the torque compensation (refer to Pr.07-26 torque compensation gain)
until the current reduces and the motor does no stall.
Improper parameter settings for
speed tracking function (including
restart after momentary power loss
and restart after fault)
Correct the parameter settings for speed tracking.
1. Start the speed tracking function.
2. Adjust the maximum current for Pr.07-09 speed tracking.
Summary of Contents for CFP2000 Series
Page 3: ......
Page 12: ...Chapter 1 Introduction CFP2000 1 3 1 2 Model Name 1 3 Serial Number ...
Page 15: ...Chapter 1 Introduction CFP2000 1 6 Frame B RFI 1 RFI 1 RFI 1 RFI 2 RFI 2 RFI 2 Figure 1 5 ...
Page 37: ...Chapter 1 Introduction CFP2000 1 28 1 7 Digital Keypad KPC CC01 ...
Page 42: ...Chapter 3 Unpacking CFP2000 3 1 Chapter 3 Unpacking 3 1 Unpacking 3 2 The Lifting Hook ...
Page 54: ...Chapter 4 Wiring CFP2000 4 5 Figure 4 4 ...
Page 57: ...Chapter 4 Wiring CFP2000 4 8 4 4 Basic Waterproof Component Wiring Diagram Frame A Frame B ...
Page 58: ...Chapter 4 Wiring CFP2000 4 9 Frame C D0 ...
Page 75: ...Chapter 5 Main Circuit Terminals CFP2000 5 16 This page intentionally left blank ...
Page 120: ...Chapter 7 Optional Accessories CFP2000 7 35 Wall Mounting Embedded Mounting ...
Page 137: ...Chapter 7 Optional Accessories CFP2000 7 52 This page intentionally left blank ...
Page 173: ...Chapter 9 Specifications CFP2000 9 8 9 5 Efficiency Curve Figure 9 5 ...
Page 251: ...Chapter 11 Summary of Parameter Settings CFP2000 11 42 This page intentionally left blank ...
Page 304: ...Chapter 12 Description of Parameter Settings CFP2000 12 1 03 3 3 4 5 ...
Page 305: ...Chapter 12 Description of Parameter Settings CFP2000 12 1 03 4 6 7 8 ...
Page 306: ...Chapter 12 Description of Parameter Settings CFP2000 12 1 03 5 9 10 11 ...
Page 307: ...Chapter 12 Description of Parameter Settings CFP2000 12 1 03 6 12 13 14 ...
Page 308: ...Chapter 12 Description of Parameter Settings CFP2000 12 1 03 7 15 16 17 ...
Page 309: ...Chapter 12 Description of Parameter Settings CFP2000 12 1 03 8 18 19 20 ...
Page 310: ...Chapter 12 Description of Parameter Settings CFP2000 12 1 03 9 21 22 23 ...
Page 311: ...Chapter 12 Description of Parameter Settings CFP2000 12 1 03 10 24 25 26 ...
Page 312: ...Chapter 12 Description of Parameter Settings CFP2000 12 1 03 11 27 28 29 ...
Page 313: ...Chapter 12 Description of Parameter Settings CFP2000 12 1 03 12 30 31 32 ...
Page 314: ...Chapter 12 Description of Parameter Settings CFP2000 12 1 03 13 33 34 35 ...
Page 315: ...Chapter 12 Description of Parameter Settings CFP2000 12 1 03 14 36 37 38 ...
Page 326: ...Chapter 12 Description of Parameter Settings CFP2000 12 1 03 25 ...
Page 545: ...Chapter 14 Fault Codes and Descriptions CFP2000 14 50 This page intentionally left blank ...
Page 726: ...Chapter 16 PLC Function Applications CFP2000 16 153 ...
Page 728: ...Chapter 16 PLC Function Applications CFP2000 16 155 ...
Page 731: ...Chapter 16 PLC Function Applications CFP2000 16 158 This page intentionally left blank ...
Page 747: ...Chapter 17 Introduction to BACnet CFP2000 17 16 This page intentionally left blank ...