Chapter 12 Description of Parameter Settings
CFP2000
12.1-02-15
Settings
Functions
Descriptions
69
Preheating output
indication
Active when the preheating is detected.
70
FAN warning detection
output
The terminal works when the internal fan warning activates.
Remote IO function is added to directly make the drive control its AO/DO and read current AI/DI
status through the standard Modbus. The corresponding index of 26xx is as follows.
bit15 bit14 bit13 bit12 bit11 bit10 bit9
bit8
bit7
bit6
bit5
bit4 bit3
bit2
bit1
bit0
2600h MI15 MI14 MI13 MI12 MI11 MI10 MI8
MI7
MI6
MI5
MI4
MI3 MI2
MI1
REV
FWD
2640h
-
-
-
-
-
MO15 MO14 MO13 MO12 MO11 MO10
-
-
RY3
RY2
RY1
2660h
AVI1
-
-
-
-
-
-
-
-
-
-
-
-
-
-
2661h
ACI
-
-
-
-
-
-
-
-
-
-
-
-
-
-
2662h
AVI2
-
-
-
-
-
-
-
-
-
-
-
-
-
-
266Ah
AI10
-
-
-
-
-
-
-
-
-
-
-
-
-
-
266Bh
AI11
-
-
-
-
-
-
-
-
-
-
-
-
-
-
26A0h
AFM1
-
-
-
-
-
-
-
-
-
-
-
-
-
26A1h
AFM2
-
-
-
-
-
-
-
-
-
-
-
-
-
26AAh
AO10
-
-
-
-
-
-
-
-
-
-
-
-
-
26ABh
AO11
-
-
-
-
-
-
-
-
-
-
-
-
-
In addition, the AI and DI values can be read directly, and DO and AO have to be controlled by
Modbus for corresponding parameter functions. The tables below shown the related parameter
definition.
DO
Terminal
Pr. Setting
Direct control the index corresponded to Modbus
RY1
Pr.02-13 = 51
bit0 of 2640h
RY2
Pr.02-14 = 51
bit1 of 2640h
RY3
Pr.02-15 = 51
bit2 of 2640h
MO10 / RY10
Pr.02-36 = 51
bit5 of 2640h
MO11 / RY11
Pr.02-37 = 51
bit6 of 2640h
MO12
Pr.02-38 = 51
bit7 of 2640h
MO13
Pr.02-39 = 51
bit8 of 2640h
MO14
Pr.02-40 = 51
bit9 of 2640h
MO15
Pr.02-41 = 51
bit10 of 2640h
AO
Terminal
Pr. Setting
Direct control the index corresponded to Modbus
AFM1
Pr.03-20 = 21
The value of 26A0h
AFM2
Pr.03-23 = 21
The value of 26A1h
AFM10
Pr.14-12 = 21
The value of 26AAh
AFM11
Pr.14-13 = 21
The value of 26ABh
Multi-function Output Direction
Default: 0000h
Settings 0000h–FFFFh (0: N.O.; 1: N.C.)
This parameter is in hexadecimal.
This parameter is set by a bit. If the bit is 1, the corresponding multi-function output acts in an
opposite way.
Example: Assume Pr.02-13=1 (indication when the drive is operating). If the output is positive, the
bit is set to 0, and then Relay is ON when the drive runs and is OFF when the drive stops. On the
contrary, if the output is negative, and the bit is set to 1, then the Relay is OFF when the drive
runs and is ON when the drive stops.
bit15 bit14 bit13 bit12 bit11 bit10 bit9 bit8 bit7 bit6 bit5 bit4 bit3 bit2 bit1 bit0
MO20 MO19 MO18 MO17 MO16 MO15 MO14 MO13 MO12 MO11 MO10 Reserved RY3 RY2 RY1
Summary of Contents for CFP2000 Series
Page 3: ......
Page 12: ...Chapter 1 Introduction CFP2000 1 3 1 2 Model Name 1 3 Serial Number ...
Page 15: ...Chapter 1 Introduction CFP2000 1 6 Frame B RFI 1 RFI 1 RFI 1 RFI 2 RFI 2 RFI 2 Figure 1 5 ...
Page 37: ...Chapter 1 Introduction CFP2000 1 28 1 7 Digital Keypad KPC CC01 ...
Page 42: ...Chapter 3 Unpacking CFP2000 3 1 Chapter 3 Unpacking 3 1 Unpacking 3 2 The Lifting Hook ...
Page 54: ...Chapter 4 Wiring CFP2000 4 5 Figure 4 4 ...
Page 57: ...Chapter 4 Wiring CFP2000 4 8 4 4 Basic Waterproof Component Wiring Diagram Frame A Frame B ...
Page 58: ...Chapter 4 Wiring CFP2000 4 9 Frame C D0 ...
Page 75: ...Chapter 5 Main Circuit Terminals CFP2000 5 16 This page intentionally left blank ...
Page 120: ...Chapter 7 Optional Accessories CFP2000 7 35 Wall Mounting Embedded Mounting ...
Page 137: ...Chapter 7 Optional Accessories CFP2000 7 52 This page intentionally left blank ...
Page 173: ...Chapter 9 Specifications CFP2000 9 8 9 5 Efficiency Curve Figure 9 5 ...
Page 251: ...Chapter 11 Summary of Parameter Settings CFP2000 11 42 This page intentionally left blank ...
Page 304: ...Chapter 12 Description of Parameter Settings CFP2000 12 1 03 3 3 4 5 ...
Page 305: ...Chapter 12 Description of Parameter Settings CFP2000 12 1 03 4 6 7 8 ...
Page 306: ...Chapter 12 Description of Parameter Settings CFP2000 12 1 03 5 9 10 11 ...
Page 307: ...Chapter 12 Description of Parameter Settings CFP2000 12 1 03 6 12 13 14 ...
Page 308: ...Chapter 12 Description of Parameter Settings CFP2000 12 1 03 7 15 16 17 ...
Page 309: ...Chapter 12 Description of Parameter Settings CFP2000 12 1 03 8 18 19 20 ...
Page 310: ...Chapter 12 Description of Parameter Settings CFP2000 12 1 03 9 21 22 23 ...
Page 311: ...Chapter 12 Description of Parameter Settings CFP2000 12 1 03 10 24 25 26 ...
Page 312: ...Chapter 12 Description of Parameter Settings CFP2000 12 1 03 11 27 28 29 ...
Page 313: ...Chapter 12 Description of Parameter Settings CFP2000 12 1 03 12 30 31 32 ...
Page 314: ...Chapter 12 Description of Parameter Settings CFP2000 12 1 03 13 33 34 35 ...
Page 315: ...Chapter 12 Description of Parameter Settings CFP2000 12 1 03 14 36 37 38 ...
Page 326: ...Chapter 12 Description of Parameter Settings CFP2000 12 1 03 25 ...
Page 545: ...Chapter 14 Fault Codes and Descriptions CFP2000 14 50 This page intentionally left blank ...
Page 726: ...Chapter 16 PLC Function Applications CFP2000 16 153 ...
Page 728: ...Chapter 16 PLC Function Applications CFP2000 16 155 ...
Page 731: ...Chapter 16 PLC Function Applications CFP2000 16 158 This page intentionally left blank ...
Page 747: ...Chapter 17 Introduction to BACnet CFP2000 17 16 This page intentionally left blank ...