Figure 69. Disconnect Extension Arm from Rail Bracket
b. Press the tab on the cable management arm, and disconnect the arm from the bracket.
Figure 70. Disconnect Cable Management Arm from Bracket
6.
Remove the upper cable management arm.
a. Press down on the blue release tab, and disconnect the extension arm from the rail bracket.
b. Press the tab on the cable management arm, and disconnect the arm from the bracket.
Install the Cable Management Arms
Installation of the cable management arms must be performed during a scheduled maintenance window when the Storage Center
system is unavailable to the network.
About this task
Install the cable management arms into a rack with a depth of 1200 mm (47.2 in.).
Replacing SCv360 Expansion Enclosure Components
57