Updating Firmware Images and Monitoring the PDU Power Status
Sample output:
3
After the process is completed, the new firmware and fan table versions
display on the screen.
Verifying and Updating the Fan Controller Board
Firmware Via SNMP
NOTE:
The following procedure applies only when there are no compute sleds
installed in the server enclosure.
When the PowerEdge C8000 server enclosure is fully populated with five
storage sleds only, you can use Simple Network Management Protocol
(SNMP) to verify and update the fan controller board (FCB) firmware. The
FCB is integrated with an Ethernet connector and supports SNMP v2c that
allows you to monitor the server enclosure status over the network and send
traps or notifications when critical situations occur.
Before You Begin
1
Install a SNMP utility on your computer. You can install a commercial or a
free SNMP utility.
[root@localhost]#./fcbutil_linux64 fcb_fw.bin
FCB Update Utility Ver 0.01.01, 2013/05/24
IPMIVer=02 FWVer=02.20 AuxFW=06000000
FCBVer=02.26 FanTableVer=01.63
Start Copy Image to BMC
100%
Wait: Copy Image to FCB and Update FCB
Done: Update Completed.
Reset BMC!
Wait: BMC Reboot and Connect to FCB
FCBVer=02.27 FanTableVer=01.63
Completed!
[root@localhost]#
Summary of Contents for PowerEdge C8000
Page 1: ...Dell PowerEdge C8000 Hardware Owner s Manual Regulatory Model B10S Regulatory Type B10S001 ...
Page 41: ...About the System 41 Figure 1 24 Service Tag Location for C8000XD Storage Sled ...
Page 160: ...160 Using the System Setup Program MIB Tree Diagram for FCB ...
Page 170: ...170 Using the System Setup Program MIB Tree Diagram for PMC ...
Page 185: ...Using the System Setup Program 185 ...
Page 186: ...186 Using the System Setup Program ...
Page 220: ...220 Installing System Components ...
Page 250: ...250 Rack Mount Configuration ...
Page 274: ...274 Troubleshooting ...
Page 288: ...288 Jumpers and Connectors ...
Page 290: ...290 Getting Help ...