Temperature
Specifications
altitude less than
950 m or 3117 ft)
Fresh air
For information on fresh air, see Expanded Operating Temperature section.
Maximum
temperature
gradient
(operating and
storage)
20°C/h (68°F/h)
Relative
humidity
Specifications
Storage
5% to 95% RH with 33°C (91°F) maximum dew point. Atmosphere must be non-condensing at all times.
Operating
10% to 80% Relative Humidity with 29°C (84.2°F) maximum dew point.
Maximum
vibration
Specifications
Operating
0.26 G
rms
at 5 Hz to 350 Hz (operation orientation).
Storage
1.88 G
rms
at 10 Hz to 500 Hz for 15 min (all six sides tested).
Maximum
shock
Specifications
Operating
Six consecutively executed shock pulses in the positive and negative x, y, and z axes of 40 G for up to 2.3 ms.
Storage
Six consecutively executed shock pulses in the positive and negative x, y, and z axes (one pulse on each side of
the system) of 71 G for up to 2 ms.
Maximum
altitude
Specifications
Operating
30482000 m (10,0006560 ft).
Storage
12,000 m (39,370 ft).
Operating
temperature
de-rating
Specifications
Up to 35 °C (95
°F)
Maximum temperature is reduced by 1°C/300 m (33.8°F/984.25 ft) above 950 m (3,117 ft)
35 °C to 40 °C
(95 °F to 104 °F)
Maximum temperature is reduced by 1°C/175 m (1°F/574.14 ft) above 950 m (3,117 ft).
40 °C to 45 °C
(104 °F to 113 °F)
Maximum temperature is reduced by 1°C/125 m (1°F/410.1 ft) above 950 m (3,117 ft).
The following section defines the limits to help avoid IT equipment damage and/or failure from particulates and gaseous contamination. If
the levels of particulates or gaseous pollution are beyond the specified limits and cause equipment damage or failure, you may need to
rectify the environmental conditions. Remediation of environmental conditions is the responsibility of the customer.
Particulate
contamination
Specifications
Air filtration
Data center air filtration as defined by ISO Class 8 per ISO 14644-1 with a 95% upper confidence limit.
NOTE:
Applies to data center environments only. Air filtration requirements do not apply to IT
equipment designed to be used outside a data center, in environments such as an office or factory
floor.
Technical specifications
31
Summary of Contents for E35S001
Page 2: ......
Page 164: ...164 Getting help ...