![Dell Chassis Management Controller User Manual Download Page 195](http://html.mh-extra.com/html/dell/chassis-management-controller/chassis-management-controller_user-manual_85064195.webp)
– Server Performance Over Power Redundancy
– Enable Dynamic Power Supply Engagement
– Disable Chassis Power Button
– Allow 110 VAC Operation
– Max Power Conservation Mode
– Enable Remote Power Logging 300 Managing and Monitoring Power
– Remote Power Logging Interval
3.
Click Apply to save the changes.
Configuring Power Budget and Redundancy Using RACADM
NOTE: To perform power management actions, you must have Chassis Configuration Administrator privilege.
To enable and set the redundancy policy:
1.
Open a serial/Telnet/SSH text console to CMC and log in.
2.
Set properties as needed:
– To select a redundancy policy, type:
racadm config -g cfgChassisPower -o
cfgChassisRedundancyPolicy <value>
where <value> is 0 (No Redundancy), 1 (AC Redundancy), 2 (Power Supply Redundancy). The default is 0.
For example, the following command sets the redundancy policy to 1:
racadm config -g cfgChassisPower -o
cfgChassisRedundancyPolicy 1
– To set the power budget value, type:
racadm config -g cfgChassisPower -o
cfgChassisPowerCap <
value
>
where <
value
> is a number between 2715–16685 representing the maximum power limit in watts. The
default is 16685.
For example, the following command sets the maximum power budget to 5400 watts:
racadm config -g cfgChassisPower -o
cfgChassisPowerCap 5400
.
– To enable or disable dynamic PSU engagement, type:
racadm config -g cfgChassisPower -o
cfgChassisDynamicPSUEngagementEnable <
value
>
where <value> is 0 (disable), 1 (enable). The default is 0.
For example, the following command disables dynamic PSU engagement:
racadm config -g cfgChassisPower -o
cfgChassisDynamicPSUEngagementEnable 0
.
– To enable the maximum power consumption mode, type:
racadm config -g cfgChassisPower -o
cfgChassisMaxPowerConservationMode 1
– To restore normal operation, type:
racadm config -g cfgChassisPower -o
cfgChassisMaxPowerConservationMode 0
195
Summary of Contents for Chassis Management Controller
Page 1: ...Dell Chassis Management Controller Firmware Version 4 3 User s Guide ...
Page 42: ...42 ...
Page 56: ...56 ...
Page 84: ...84 ...
Page 98: ...98 ...
Page 104: ...104 ...
Page 130: ...130 ...
Page 136: ...136 ...
Page 200: ...200 ...
Page 214: ...214 ...