4. Select the
normally open contact
.
a. Set the function to
ICC > Inputs > 5 > Inter-Controller Communication In 1
(where
5
is the Controller ID of the BUS
TIE breaker controller).
b. Select
Save
from the
Functions
menu.
5. Select the
normally open coil
.
a. Set the function to
Power management > Activate power management rule 3
.
b. Select
Save
from the
Functions
menu.
6. Select
Write
from the right side panel.
Enable CustomLogic
BUS TIE breaker Controller:
1. Connect to the BUS TIE breaker controller.
2. Go to
Configure > Parameters
.
3. Enable
CustomLogic
under
Utility > CustomLogic
.
4. Select
Write
from the right side panel.
GENSET controller 1:
1. Connect to GENSET controller 1.
2. Go to
Configure > Parameters
.
3. Enable
CustomLogic
under
Utility > CustomLogic
.
4. Select
Write
from the right side panel.
GENSET controller 3:
1. Connect to GENSET controller 3.
2. Go to
Configure > Parameters
.
3. Enable
CustomLogic
under
Utility > CustomLogic
.
4. Select
Write
from the right side panel.