3.
Select the first
rising edge contact
.
a. Set the function to
Inputs > Terminal(s) x, y, z, Slot #
. (The first digital input configured in
Configure the output
,
step 3.)
b. Select
Save
from the
Functions
menu.
4.
Select the
timer
.
a. Set the
Mode
to
TP
(pulse timer).
b. Set the
Preset
to
10
.
c. Set the
Units
to
seconds
.
d. Select
Save
from the
Functions
menu.
5.
Select the second
rising edge contact
.
a. Set the function to
Inputs > Terminal(s) x, y, z, Slot #
. (The second digital input configured in
Configure the
output
, step 3.)
b. Select
Save
from the
Functions
menu.
6.
Select the
normally closed contact
.
a. Set the function to
Alarm > Inputs > Any unacknowledged alarm
.
b. Select
Save
from the
Functions
menu.
7.
Add a
Normally open contact
, a
Rising edge contact
, a
Normally open coil
and a
Reset coil
to the logic grid. Connect the elements to each other on the logic grid as shown in the diagram below. The rising
edge contact and reset coil must be in parallel to the normally open coil.
8.
Select the
normally open coil
.
a. Set the function to
Outputs > Terminal(s) x, y, z, Slot #
. (The digital output configured in
Configure the output
,
step 2.)
b. Select
Save
from the
Functions
menu.
9.
Select the
rising edge contact
.
a. Set the function to
Inputs > Terminal(s) x, y, z, Slot #
. (The third digital input configured in
Configure the output
,
step 3.)
b. Select
Save
from the
Functions
menu.
10. Select
Write
from the right side panel.