3. Add a
Normally open contact
and a
Normally open coil
to the logic grid and connect them to each other.
Add another
Normally open contact
and a
Normally open coil
to the logic grid and connect them to each
other.
4. Select the
normally open contact
in line 1.
a. Set the function to
Breakers > Bus tie breaker > Outputs > State > BTB is open
.
b. Select
Save
from the
Functions
menu.
5. Select the
normally open contact
in line 2.
a. Set the function to
Breakers > Bus tie breaker > Outputs > State > BTB is closed
.
b. Select
Save
from the
Functions
menu.
6. Select the
normally open coil
in line 1.
a. Set the function to
ICC > Outputs > Inter-Controller Communication Out 1
.
b. Select
Save
from the
Functions
menu.
7. Select the
normally open coil
in line 2.
a. Set the function to
ICC > Outputs > Inter-Controller Communication Out 2
.
b. Select
Save
from the
Functions
menu.
8. Select
Write
from the right side panel.
9. Recommended: Enable
CustomLogic
on controller 1 before connecting to controller 2.
See
Enable CustomLogic
below.
GENSET controller 1:
1. Connect to GENSET controller 1.
2. Go to
Configure > CustomLogic > Logic creator
and create a
New
Project
with one
Section
and one
Block
.
PPM 300 PICUS manual 4189341080 UK