b. Select
Save
from the
Functions
menu.
6. Select
Write
from the right side panel.
7. Recommended: Enable
CustomLogic
on controller 1 before connecting to controller 2.
See
Enable CustomLogic
below.
Controller 2:
1. Connect to controller 2.
2. Go to
Configure > CustomLogic > Logic creator
and create a
New
Project
with one
Section
and one
Block
.
3. Add a
Normally open contact
, a
Normally closed contact
, a
Timer
and two
Normally open coils
to the logic grid and connect them to each other. The
normally open coils
must be connected in parallel to each
other.
4. Select the
normally open contact
.
a. Set the function to
ICC > Inputs > # > Inter-Controller Communication In 1
(where
#
is the Controller ID of
controller 1).
b. Select
Save
from the
Functions
menu.
INFO
The number of the
Inter-Controller Communication In
on the receiving controller must be the same as the
number of the
Inter-Controller Communication Out
on the sending controller.
5. Select the
timer
.
a. Set the
Preset
to
5
.
b. Set the
Units
to
seconds
.
c. Select
Save
from the
Functions
menu.
6. Select one of the
normally open coils
.
a. Set the function to
Inputs > Terminal(s) x, y, z, Slot #
(The digital output configured in step 9).
b. Select
Save
from the
Functions
menu.
PPM 300 PICUS manual 4189341080 UK
www.deif.com