t [s]
175ZA052.12
fOUT = 2 x f M,N
fOUT = 0.2 x f M,N
fOUT = 1 x f M,N(par. 1-23)
I
MN
(par. 1-24)
I
M
WARNING
In order to maintain PELV, all connections made to the
control terminals must be PELV, e.g. thermistor must be
reinforced/ double insulated
NOTE
Danfoss recommends using 24V DC as thermistor supply
voltage.
NOTE
The ETR timer function does not work when
= [1] PM, non salient SPM.
NOTE
For correct operation of ETR function setting in
must fit the application (see description of
1-91 Motor External Fan
Option: Function:
[0]
*
No No external fan is required, i.e. the motor is derated at
low speed.
[1]
Yes Applies an external motor fan (external ventilation), so
no derating of the motor is required at low speed. The
upper curve in graph above (fout = 1 x fM,N) is
followed if the motor current is lower than nominal
motor current (see
). If the motor
current exceeds nominal current, the operation time
still decreases as if no fan were installed.
1-93 Thermistor Source
Option:
Function:
Select the input to which the thermistor
(PTC sensor) should be connected. An
analog input option [1] or [2] cannot be
selected if the analog input is already in
use as a reference source (selected in
or
When using MCB 112, choice [0]
None
must always be selected.
[0]
*
None
[1]
Analog input 53
[2]
Analog input 54
[3]
Digital input 18
[4]
Digital input 19
[5]
Digital input 32
[6]
Digital input 33
NOTE
This parameter cannot be adjusted while the motor is
running.
NOTE
Digital input should be set to [0]
PNP - Active at 24V
in
.
Parameter Description
VLT
®
HVAC Drive Programming Guide
48
MG.11.CC.02 - VLT
®
is a registered Danfoss trademark