3.11 Main Menu - CAN Fieldbus - Group 10
3.11.1 10-** DeviceNet and CAN Fieldbus
3.11.2 10-0* Common Settings
10-00 CAN Protocol
Option:
Function:
[1]
*
DeviceNet
View the active CAN protocol.
NOTE
The parameter options depend on installed option.
10-01 Baud Rate Select
Option:
Function:
Select the fieldbus transmission speed. The
selection must correspond to the transmission
speed of the master and the other fieldbus
nodes.
[16]
10 Kbps
[17]
20 Kbps
[18]
50 Kbps
[19]
100 Kbps
[20]
*
125 Kbps
[21]
250 Kbps
[22]
500 Kbps
[23]
800 Kbps
[24]
1000 Kbps
10-02 MAC ID
Range:
Function:
Size related
*
[ 0 - 63. ] Selection of station address. Every
station connected to the same
DeviceNet network must have an
unambiguous address.
10-05 Readout Transmit Error Counter
Range:
Function:
0
*
[0 - 255 ] View the number of CAN control transmission
errors since the last power-up.
10-06 Readout Receive Error Counter
Range:
Function:
0
*
[0 - 255 ] View the number of CAN control receipt errors
since the last power-up.
10-07 Readout Bus Off Counter
Range:
Function:
0
*
[0 - 255 ] View the number of Bus Off events since the last
power-up.
3.11.3 10-1* DeviceNet
10-10 Process Data Type Selection
Option:
Function:
Select the Instance (telegram) for data
transmission. The Instances available are
dependent upon the setting of
.
When
is set to [0]
FC
profile
,
10-10 Process Data Type Selection
options [0] and [1] are available.
When
is set to [5]
ODVA
,
10-10 Process Data Type Selection
options [2]
and [3] are available.
Instances 100/150 and 101/151 are Danfoss-
specific. Instances 20/70 and 21/71 are
ODVA-specific AC Drive profiles.
For guidelines in telegram selection, please
refer to the
DeviceNet Operating Instructions
.
Note that a change to this parameter will
be executed immediately.
[0]
*
INSTANCE
100/150
[1]
INSTANCE
101/151
[2]
INSTANCE
20/70
[3]
INSTANCE
21/71
10-11 Process Data Config Write
Option:
Function:
Select the process
write data for I/O
Assembly Instances
101/151. Elements [2]
and [3] of this array
can be selected.
Elements [0] and [1]
of the array are fixed.
[0]
*
None
[302]
Minimum Reference
[303]
Maximum Reference
[341]
Ramp 1 Ramp Up Time
[342]
Ramp 1 Ramp Down Time
[351]
Ramp 2 Ramp Up Time
[352]
Ramp 2 Ramp Down Time
[380]
Jog Ramp Time
[381]
Quick Stop Ramp Time
[382]
Starting Ramp Up Time
[411]
Motor Speed Low Limit [RPM]
[413]
Motor Speed High Limit [RPM]
[416]
Torque Limit Motor Mode
Parameter Description
VLT
®
HVAC Drive Programming Guide
MG.11.CC.02 - VLT
®
is a registered Danfoss trademark
93
3