9-53 Profibus Warning Word
Range:
Function:
0
*
[0 - 65535 ] This parameter displays Profibus communi-
cation warnings. Please refer to the
Profibus
Operating Instructions
for further information.
Read only
Bit:
Meaning:
0
Connection with DP-master is not ok
1
Not used
2
FDLNDL (Fieldbus Data link Layer) is not ok
3
Clear data command received
4
Actual value is not updated
5
Baudrate search
6
PROFIBUS ASIC is not transmitting
7
Initialisation of PROFIBUS is not ok
8
Frequency converter is tripped
9
Internal CAN error
10
Wrong configuration data from PLC
11
Wrong ID sent by PLC
12
Internal error occured
13
Not configured
14
Timeout active
15
Warning 34 active
9-63 Actual Baud Rate
Option:
Function:
This parameter displays the actual
Profibus baud rate. The Profibus
Master automatically sets the baud
rate.
[0]
9,6 kbit/s
[1]
19,2 kbit/s
[2]
93,75 kbit/s
[3]
187,5 kbit/s
[4]
500 kbit/s
[6]
1500 kbit/s
[7]
3000 kbit/s
[8]
6000 kbit/s
[9]
12000 kbit/s
[10]
31,25 kbit/s
[11]
45,45 kbit/s
[255]
*
No baudrate found
9-65 Profile Number
Range:
Function:
0
*
[0 - 0 ] This parameter contains the profile identification.
Byte 1 contains the profile number and byte 2 the
version number of the profile.
NOTE
This parameter is not visible via LCP.
9-70 Programming Set-up
Option:
Function:
Select the set-up to be edited.
[0]
Factory setup Uses default data. This option can be used
as a data source to return the other set-ups
to a known state.
[1]
Set-up 1
Edits Set-up 1.
[2]
Set-up 2
Edits Set-up 2.
[3]
Set-up 3
Edits Set-up 3.
[4]
Set-up 4
Edits Set-up 4.
[9]
*
Active Set-up Follows the active set-up selected in
.
This parameter is unique to LCP and fieldbuses. See also
.
9-71 Profibus Save Data Values
Option:
Function:
Parameter values changed via Profibus are not
automatically stored in non-volatile memory.
Use this parameter to activate a function that
stores parameter values in the EEPROM non-
volatile memory, so changed parameter values
will be retained at power-down.
[0]
*
Off
Deactivates the non-volatile storage function.
[1]
Store all
setups
Stores all parameter values for all set-ups in the
non-volatile memory. The selection returns to
Off
[0] when all parameter values have been
stored.
[2]
Store all
setups
Stores all parameter values for all set-ups in the
non-volatile memory. The selection returns to
Off
[0] when all parameter values have been
stored.
9-72 ProfibusDriveReset
Option:
Function:
[0]
*
No action
[1]
Power-on
reset
Resets frequency converter upon power-up,
as for power-cycle.
[3]
Comm option
reset
Resets the Profibus option only, useful after
changing certain settings in parameter
group 9-**, e.g.
When reset, the frequency converter
disappears from the fieldbus, which may
cause a communication error from the
master.
Parameter Description
VLT
®
HVAC Drive Programming Guide
MG.11.CC.02 - VLT
®
is a registered Danfoss trademark
91