3.7.7 5-6* Pulse Outputs
Parameters for configuring the scaling and output
functions of pulse outputs. The pulse outputs are
designated to terminals 27 or 29. Select terminal 27 output
in
and terminal 29 output in
.
Output value
Output
(Hz)
High output
value
P 5-60(term27)
P 5-63(term29)
High freq.
P 5-62(term27)
P 5-65(term29)
130BA089.11
Options for readout output variables:
[0]
No operation
[45]
Bus ctrl.
[48]
Bus ctrl., timeout
[100]
Output frequency
[101]
Reference
[102]
Feedback
[103]
Motor current
[104]
Torque relative to limit
[105]
Torque relative to rated
[106]
Power
[107]
Speed
[108]
Torque
[109]
Max Out Freq
[113]
Ext. Closed Loop
[114]
Ext. Closed Loop
[115]
Ext. Closed Loop
Select the operation variable assigned for terminal 27
readouts.
This parameter cannot be adjusted while the motor is
running. Same options and functions as parameter group
5-6*.
[0]
*
No operation
5-60 Terminal 27 Pulse Output Variable
Option:
Function:
[0]
*
No operation
[45]
Bus ctrl.
[48]
Bus ctrl., timeout
[90]
kWh counter pulse
5-60 Terminal 27 Pulse Output Variable
Option:
Function:
[100]
Output freq. 0-100
[101]
Reference Min-Max
[102]
Fe-200%
[103]
Motor cur. 0-Imax
[104]
Torque 0-Tlim
[105]
Torque 0-Tnom
[106]
Power 0-Pnom
[107]
Speed 0-HighLim
[113]
Ext. Closed Loop 1
[114]
Ext. Closed Loop 2
[115]
Ext. Closed Loop 3
5-62 Pulse Output Max Freq #27
Set the maximum frequency for terminal 27, corresponding to
the output variable selected in
.
This parameter cannot be adjusted while the motor is running.
Range:
Function:
5000 Hz
*
[0 - 32000 Hz]
5-63 Terminal 29 Pulse Output Variable
Select the variable for viewing on the terminal 29 display.
This parameter cannot be adjusted while the motor is running.
Same options and functions as parameter group 5-6*.
Option:
Function:
[0]
*
No operation
[45]
Bus ctrl.
[48]
Bus ctrl., timeout
[90]
kWh counter pulse
[100]
Output freq. 0-100
[101]
Reference Min-Max
[102]
Fe-200%
[103]
Motor cur. 0-Imax
[104]
Torque 0-Tlim
[105]
Torque 0-Tnom
[106]
Power 0-Pnom
[107]
Speed 0-HighLim
[113]
Ext. Closed Loop 1
[114]
Ext. Closed Loop 2
[115]
Ext. Closed Loop 3
5-65 Pulse Output Max Freq #29
Set the maximum frequency for terminal 29 corresponding to the
output variable set in
5-63 Terminal 29 Pulse Output Variable
This parameter cannot be adjusted while the motor is running.
Range:
Function:
5000 Hz
*
[0 - 32000 Hz]