8-05 End-of-Timeout Function
Option:
Function:
until
toggles. Then
the frequency converter resumes its original
set-up.
[1]
*
Resume set-
up
Resumes the set-up active prior to the time-
out.
8-06 Reset Control Timeout
Option:
Function:
This parameter is active only when the choice
Hold set-up
[0] has been selected in
.
[0]
*
Do not
reset
Retains the set-up specified in
, [Select setup 1-4] following a
control time-out.
[1]
Do reset Returns the frequency converter to the original
set-up following a control word time-out. When
the value is set to
Do reset
[1], the frequency
converter performs the reset and then
immediately reverts to the
Do not reset
[0]
setting.
8-07 Diagnosis Trigger
Option:
Function:
This parameter has no function for
BACnet.
[0]
*
Disable
[1]
Trigger on alarms
[2]
Trigger alarm/warn.
3.9.2 8-1* Ctrl. Word Settings
8-10 Control Profile
Option:
Function:
Select the interpretation of the control
and status words corresponding to the
installed fieldbus. Only the selections
valid for the fieldbus installed in slot A
will be visible in the LCP display.
[0]
*
FC profile
[1]
PROFIdrive profile
[5]
ODVA
[7]
CANopen DSP 402
8-13 Configurable Status Word STW
Option:
Function:
This parameter enables configuration of
bits 12 – 15 in the status word.
[0]
No function
[1]
*
Profile Default
Function corresponds to the profile
default selected in
.
[2]
Alarm 68 Only
Only set in case of an Alarm 68.
8-13 Configurable Status Word STW
Option:
Function:
[3]
Trip excl Alarm
68
Set in case of a trip, except if the trip is
executed by an Alarm 68.
[10] T18 DI status.
The bit indicates the status of terminal
18
*1
.
[11] T19 DI status.
The bit indicates the status of terminal
19
*1
.
[12] T27 DI status.
The bit indicates the status of terminal
27
*1
.
[13] T29 DI status.
The bit indicates the status of terminal
29
*1
.
[14] T32 DI status.
The bit indicates the status of terminal
32
*1
.
[15] T33 DI status.
The bit indicates the status of terminal
33
*1
.
[16] T37 DI status
The bit indicates the status of terminal
37
*2
.
[21] Thermal
warning
The thermal warning turns on when the
temperature exceeds the limit in the
motor, the frequency converter, the brake
resistor, or the thermistor.
[30] Brake fault
(IGBT)
Output is Logic ‘1’ when the brake IGBT is
short-circuited. Use this function to
protect the frequency converter if there is
a fault on the brake modules. Use the
output/relay to cut out the main voltage
from the frequency converter.
[40] Out of ref
range
[60] Comparator 0
See parameter group 13-1*. If Comparator
0 is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[61] Comparator 1
See parameter group 13-1*. If Comparator
1 is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[62] Comparator 2
See parameter group 13-1*. If Comparator
2 is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[63] Comparator 3
See parameter group 13-1*. If Comparator
3 is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[64] Comparator 4
See parameter group 13-1*. If Comparator
4 is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[65] Comparator 5
See parameter group 13-1*. If Comparator
5 is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[70] Logic Rule 0
See parameter group 13-4*. If Logic Rule
0 is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[71] Logic Rule 1
See parameter group 13-4*. If Logic Rule
1 is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
Parameter Description
VLT
®
HVAC Drive Programming Guide
82
MG.11.CC.02 - VLT
®
is a registered Danfoss trademark
3