8-13 Configurable Status Word STW
Option:
Function:
[72] Logic Rule 2
See parameter group 13-4*. If Logic Rule
2 is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[73] Logic Rule 3
See parameter group 13-4*. If Logic Rule
3 is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[74] Logic Rule 4
See parameter group 13-4*. If Logic Rule
4 is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[75] Logic Rule 5
See parameter group 13-4*. If Logic Rule
5 is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[80] SL Digital
Output A
See
. The output
will go high whenever the Smart Logic
Action [38] Set dig. out. A high is
executed. The output will go low
whenever the Smart Logic Action [32] Set
dig. out. A low is executed.
[81] SL Digital
Output B
See
. The input
will go high whenever the Smart Logic
Action [39] Set dig. out. A high is
executed. The input will go low whenever
the Smart Logic Action [33] Set dig. out. A
low is executed. [
[82] SL Digital
Output C
See
. The input
will go high whenever the Smart Logic
Action [40] Set dig. out. A high is
executed. The input will go low whenever
the Smart Logic Action [34] Set dig. out. A
low is executed.
[83] SL Digital
Output D
See
. The input
will go high whenever the Smart Logic
Action [41] Set dig. out. A high is
executed. The input will go low whenever
the Smart Logic Action [35] Set dig. out. A
low is executed.
[84] SL Digital
Output E
See
. The input
will go high whenever the Smart Logic
Action [42] Set dig. out. A high is
executed. The input will go low whenever
the Smart Logic Action [36] Set dig. out. A
low is executed.
[85] SL Digital
Output F
See
. The input
will go high whenever the Smart Logic
Action [43] Set dig. out. A high is
executed. The input will go low whenever
the Smart Logic Action [37] Set dig. out. A
low is executed.
*1
: “0” indicates that the terminal is low
“1” indicates that the terminal is high
*1
: “0” indicates T37 is low (safe stop)
“1” indicates T37 is high (normal)
3.9.3 8-3* FC Port Settings
8-30 Protocol
Option:
Function:
Protocol selection for the integrated FC
(standard) Port (RS485) on the control card.
Parameter group 8-7* is only visible when FC
Option [9] is chosen.
[0]
*
FC
Communication according to the FC Protocol as
described in the
VLT
®
HVAC Drive Design Guide,
RS485 Installation and Set-up
.
[1]
FC MC
Same as FC [0] but to be used when
downloading SW to the frequency converter or
uploading dll file (covering information
regarding parameters available in the frequency
converter and their inter-dependencies) to
Motion Control Tool MCT10.
[2]
Modbus
RTU
Communication according to the Modbus RTU
protocol as described in the
VLT
®
HVAC Drive
Design Guide, RS485 Installation and Set-up
.
[3]
Metasys
N2
Communication protocol. The N2 software
protocol is designed to be general in nature in
order to accommodate the unique properties
each device may have. Please see separate
manual
VLT
®
HVAC Drive Metasys MG.11.GX.YY
.
[4]
FLN
Communication according to the Apogee FLN
P1 protocol.
[5]
BACnet
Communication according to an open data
communications protocol (Building Automation
and Control Network), American National
Standard (ANSI/ASHRAE 135-1995).
[9]
FC
Option
To be used when a gateway is connected to the
integrated RS485 port, e.g. the BACnet gateway.
Following changes will take place:
-Address for the FC port will be set to 1 and
, is now used to set the address for
the gateway on the network, e.g. BACnet.
Please see separate manual
VLT
®
HVAC Drive
BACnet, MG.11.DX.YY
.
-Baud rate for the FC port will be set to a fixed
value (115.200 Baud) and
, is now
used to set the baud rate for the network port
(e.g. BACnet) on the gateway.
[20] LEN
NOTE
Further details can be found in the Metasys manual, MG.
11.GX.YY.
Parameter Description
VLT
®
HVAC Drive Programming Guide
MG.11.CC.02 - VLT
®
is a registered Danfoss trademark
83