3.13.4 13-2* Timers
Use the result (TRUE or FALSE) from
timers
directly to
define an
event
(see
), or as
boolean input in a
logic rule
(see
or
).
A timer is only FALSE when started by an action (i.e. Start
timer 1 [29]) until the timer value entered in this
parameter is elapsed. Then it becomes TRUE again.
All parameters in this parameter group are array
parameters with index 0 to 2. Select index 0 to program
Timer 0, select index 1 to program Timer 1, and so on.
13-20 SL Controller Timer
Array [3]
Range:
Function:
Size
related
*
[ 0.000 -
0.000 ]
Enter the value to define the duration
of the FALSE output from the
programmed timer. A timer is only
FALSE if it is started by an action (i.e.
Start timer 1
[29]) and until the given
timer value has elapsed.
3.13.5 13-4* Logic Rules
Combine up to three boolean inputs (TRUE / FALSE inputs)
from timers, comparators, digital inputs, status bits and
events using the logical operators AND, OR, and NOT.
Select boolean inputs for the calculation in
,
and
. Define the operators used to logically combine
the selected inputs in
and
. . .
. . .
. . .
. . .
Par. LC-43
Logic Rule Operator 2
Par. LC-41
Logic Rule Operator 1
Par. LC-40
Logic Rule Boolean 1
Par. LC-42
Logic Rule Boolean 2
Par. LC-44
Logic Rule Boolean 3
130BB673.10
Priority of calculation
The results of
,
and
are calculated
first. The outcome (TRUE / FALSE) of this calculation is
combined with the settings of
and
, yielding the final result
(TRUE / FALSE) of the logic rule.
13-40 Logic Rule Boolean 1
Array [6]
Option:
Function:
[0]
*
False
Enters the fixed value of FALSE in the
logic rule.
13-40 Logic Rule Boolean 1
Array [6]
Option:
Function:
[1]
True
Enters the fixed value TRUE in the
logic rule.
[2]
Running
See parameter group 5-3* for further
description.
[3]
In range
See parameter group 5-3* for further
description.
[4]
On reference
See parameter group 5-3* for further
description.
[5]
Torque limit
See parameter group 5-3* for further
description.
[6]
Current limit
See parameter group 5-3* for further
description.
[7]
Out of current
range
See parameter group 5-3* for further
description.
[8]
Below I low
See parameter group 5-3* for further
description.
[9]
Above I high
See parameter group 5-3* for further
description.
[10]
Out of speed range
[11]
Below speed low
See parameter group 5-3* for further
description.
[12]
Above speed high
See parameter group 5-3* for further
description.
[13]
Out of feedb. range See parameter group 5-3* for further
description.
[14]
Below feedb. low
See parameter group 5-3* for further
description.
[15]
Above feedb. high
See parameter group 5-3* for further
description.
[16]
Thermal warning
See parameter group 5-3* for further
description.
[17]
Mains out of range See parameter group for further
description.
[18]
Reversing
See parameter group 5-3* for further
description.
[19]
Warning
See parameter group 5-3* for further
description.
[20]
Alarm (trip)
See parameter group 5-3* for further
description.
[21]
Alarm (trip lock)
See parameter group 5-3* for further
description.
[22]
Comparator 0
Use the result of comparator 0 in the
logic rule.
[23]
Comparator 1
Use the result of comparator 1 in the
logic rule.
Parameter Description