24-02 Fire Mode Unit
Option:
Function:
[30]
kg/s
[31]
kg/min
[32]
kg/h
[33]
t/min
[34]
t/h
[40]
m/s
[41]
m/min
[45]
m
[60]
°C
[70]
mbar
[71]
bar
[72]
Pa
[73]
kPa
[74]
m WG
[75]
mm Hg
[80]
kW
[120] GPM
[121] gal/s
[122] gal/min
[123] gal/h
[124] CFM
[125] ft³/s
[126] ft³/min
[127] ft³/h
[130] lb/s
[131] lb/min
[132] lb/h
[140] ft/s
[141] ft/min
[145] ft
[160] °F
[170] psi
[171] lb/in²
[172] in WG
[173] ft WG
[174] in Hg
[180] HP
24-03 Fire Mode Min Reference
Range:
Function:
Size
related
*
[ -999999.999 -
par. 24-04
FireModeUnit]
Minimum value for the
reference/set point (limiting the
sum of value in
and value of
signal on input selected in
24-06 Fire Mode Reference Source
If running in Open loop when Fire
Mode is active, the unit is chosen
by the setting of
. For closed loop, the unit is
selected in
.
24-04 Fire Mode Max Reference
Range:
Function:
Size
related
*
[ par. 24-03 -
999999.999
FireModeUnit]
Maximum value for the
reference/set point (limiting the
sum of value in
and value of signal
on input selected in
).
If running in Open loop when Fire
Mode is active, the unit is chosen
by the setting of
. For closed loop, the unit is
selected in
.
24-05 Fire Mode Preset Reference
Range:
Function:
0.00 %
*
[-100.00 -
100.00 %]
Enter the required preset reference/set
point as a percentage of the Fire Mode
Max Reference set in
. The set value will be
added to the value represented by the
signal on the analog input selected in
24-06 Fire Mode Reference Source
.
24-06 Fire Mode Reference Source
Option:
Function:
Select the external reference input to
be used for the Fire Mode. This signal
will be added to the value set in
24-06 Fire Mode Reference Source
.
[0]
No function
[1]
Analog input 53
[2]
Analog input 54
[7]
Pulse input 29
[8]
Pulse input 33
[20] Digital pot.meter
[21] Analog input X30/11
[22] Analog input X30/12
[23] Analog Input X42/1
[24] Analog Input X42/3
[25] Analog Input X42/5
Parameter Description
VLT
®
HVAC Drive Programming Guide
MG.11.CC.02 - VLT
®
is a registered Danfoss trademark
173
3
3