6.14.2 Connecting to Control Terminals
Illustration 6.14
shows all control terminals of the frequency
converter. Applying Start (term. 18) and an analog
reference (term. 53 or 60) make the frequency converter.
run.
Illustration 6.14 Overview of Control Terminals in PNP-configu-
ration and Factory Setting.
6.15 Switches
NOTE
Do not operate switches with power on the frequency
converter.
Bus termination:
Switch
BUS TER
position ON terminates the RS-485 port,
terminals 68, 69. See
Illustration 6.12
.
Default setting = Off.
Illustration 6.15 S640 Bus Termination
S200 Switches 1-4:
Switch 1
*OFF=PNP terminals 29
ON=NPN terminals 29
Switch 2
*OFF=PNP terminal 18, 19, 27 and 33
ON=NPN terminal 18, 19, 27 and 33
Switch 3
No function
Switch 4
*OFF=Terminal 53 0-10 V
ON=Terminal 53 0/4-20 mA
*=default setting
Table 6.5 Settings for S200 Switches 1-4
Illustration 6.16 S200 Switches 1-4.
NOTE
Parameter 6-19 must be set according to Switch 4 position.
6.16 Final Set-Up and Test
To test the set-up and ensure that the frequency converter.
is running, follow these steps.
Step 1. Locate the motor name plate
The motor is either star- (Y) or delta-connected (
Δ
). This
information is located on the motor name plate data.
Step 2. Enter the motor name plate data in this parameter
list.
To access this list first press the [Quick Menu] key then
select “Q2 Quick Setup”.
1.
Motor Power [kW]
or Motor Power [HP]
1-20 Motor Power [kW]
1-21 Motor Power [HP]
2.
Motor Voltage
1-22 Motor Voltage
3.
Motor Frequency
1-23 Motor Frequency
4.
Motor Current
1-24 Motor Current
5.
Motor Nominal Speed
1-25 Motor Nominal
Speed
Table 6.6
How to Install
VLT
®
Micro Drive FC 51 Design Guide
58
MG02K202 - VLT
®
is a registered Danfoss trademark
6
6