Bit 10, Data not valid/Data valid
Tell the frequency converter whether to use or ignore the
control word.
Bit 10=’0’: The control word is ignored. Bit 10=’1’: The
control word is used. This function is relevant because the
telegram always contains the control word, regardless of
the telegram type. Turn off the control word if not wanting
to use it when updating or reading parameters.
Bit 11, Relay 01
Bit 11="0": Relay not activated.
Bit 11="1": Relay 01 activated provided that
Control word
bit 11=36
is chosen in
5-40 Function Relay
.
Bit 12, Relay 02
Bit 12="0": Relay 02 is not activated. Bit 12="1": Relay 02 is
activated provided that
Control word bit 12=37
is chosen in
5-40 Function Relay
.
Bit 13, Selection of set-up
Use bit 13 to choose from the 2 menu set-ups according
to the table.
Set-up
Bit 13
1
0
2
1
Table 8.38
The function is only possible when
Multi Set-Ups=9
is
selected in
0-10 Active Set-up
.
Make a selection in
8-55 Set-up Select
to define how Bit 13
gates with the corresponding function on the digital
inputs.
Bit 15 Reverse
Bit 15=’0’: No reversing.
Bit 15=’1’: Reversing. In the default setting, reversing is set
to digital in
8-54 Reversing Select
. Bit 15 causes reversing
only when Ser. communication, Logic or Logic and is
selected.
8.11.2 Status Word According to FC Profile
(STW) (
8-30 Protocol
= FC profile)
Output freq.
STW
Bit
no.:
Slave-master
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
130BA273.10
Illustration 8.15
Bit
Bit=0
Bit=1
00
Control not ready
Control ready
01
Drive not ready
Drive ready
02
Coasting
Enable
03
No error
Trip
04
No error
Error (no trip)
05
Reserved
-
06
No error
Triplock
07
No warning
Warning
08
Speed
≠
reference
Speed=reference
09
Local operation
Bus control
10
Out of frequency limit
Frequency limit OK
11
No operation
In operation
12
Drive OK
Stopped, auto start
13
Voltage OK
Voltage exceeded
14
Torque OK
Torque exceeded
15
Timer OK
Timer exceeded
Table 8.39
Explanation of the status bits
Bit 00, Control not ready/ready
Bit 00=’0’: The frequency converter trips.
Bit 00=’1’: The frequency converter controls are ready but
the power component does not necessarily receive any
power supply (in case of external 24 V supply to controls).
Bit 01, Drive ready
Bit 01=’1’: The frequency converter is ready for operation
but the coasting command is active via the digital inputs
or via serial communication.
Bit 02, Coasting stop
Bit 02=’0’: The frequency converter releases the motor.
Bit 02=’1’: The frequency converter starts the motor with a
start command.
Bit 03, No error/trip
Bit 03=’0’ : The frequency converter is not in fault mode.
Bit 03=’1’: The frequency converter trips. To re-establish
operation, press [Reset].
Bit 04, No error/error (no trip)
Bit 04=’0’: The frequency converter is not in fault mode. Bit
04=“1”: The frequency converter shows an error but does
not trip.
Bit 05, Not used
Bit 05 is not used in the status word.
Bit 06, No error/triplock
Bit 06=’0’: The frequency converter is not in fault mode. Bit
06=“1”: The frequency converter is tripped and locked.