6.5 Electrical Installation in General
NOTE
All cabling must comply with national and local
regulations on cable cross-sections and ambient
temperature. Copper conductors required, (60-75
°
C)
recommended.
Power [kW]
Torque [Nm]
Frame
1x200-240 V
3x200-240 V
3x380-480 V
Line
Motor
DC connection/Brake
Control Terminals
Earth
Relay
M1
0.18-0.75
0.25-0.75
0.37-0.75
1.4
0.7
Spade
1)
0.15
3
0.5
M2
1.5
1.5
1.5-2.2
1.4
0.7
Spade
1)
0.15
3
0.5
M3
2.2
2.2-3.7
3.0-7.5
1.4
0.7
Spade
1)
0.15
3
0.5
M4
11.0-15.0
1.3
1.3
1.3
0.15
3
0.5
M5
18.5-22.0
1.3
1.3
1.3
0.15
3
0.5
1)
Spade connectors (6.3 mm Faston plugs)
Table 6.2 Tightening of Terminals
How to Install
VLT
®
Micro Drive FC 51 Design Guide
MG02K202 - VLT
®
is a registered Danfoss trademark
49