6.7 Mains Connection
Step 1: Mount earth cable.
Step 2: Mount wires in terminals L1/L, L2 and L3/N and
tighten.
Illustration 6.4 Mounting of Earth Cable and Mains Wires
For 3-phase connection, connect wires to all three
terminals.
For single-phase connection, connect wires to terminals
L1/L and L3/N.
Illustration 6.5 Three-phase and Single-phase Wire Connections
6.8 Motor Connection
6.8.1 How to Connect the Motor
See
9 Specifications
for correct dimensioning of motor
cable cross-section and length.
•
Use a shielded/armored motor cable to comply
with EMC emission specifications, and connect
this cable to both the decoupling plate and the
motor metal.
•
Keep motor cable as short as possible to reduce
the noise level and leakage currents.
For further details on mounting of the decoupling plate,
see
instruction MI02B
.
All types of three-phased asynchronous standard motors
can be connected to the frequency converter. Normally,
small motors are star-connected (230/400 V,
Δ
/Y). Large
motors are delta-connected (400/690 V,
Δ
/Y). Refer to
motor nameplate for correct connection and voltage.
Illustration 6.6 Star and Delta Connections
Step 1: Mount the earth cable.
Step 2: Connect wires to terminals either in star or delta-
connection. See motor nameplate for further information.
Illustration 6.7 Mounting of Earth Cable and Motor Wires
For EMC correct installation, use optional de-coupling
plate, see
5.2 Options for VLT Micro Drive
.
Illustration 6.8 Frequency Converter with De-coupling Plate
6.8.2 Motor Cables
See
9 Specifications
for maximum dimensioning of motor
cable cross-section and length.
•
Use a screened/armoured motor cable to comply
with EMC emission specifications.
•
Keep the motor cable as short as possible to
reduce the noise level and leakage currents.