9.1.3 Mains Supply 3x380-480 V AC
Normal overload 150% for 1 min
Frequency converter
Typical Shaft Output [kW]
PK37
0.37
PK75
0.75
P1K5
1.5
P2K2
2.2
P3K0
3.0
P4K0
4.0
Typical Shaft Output [HP]
0.5
1
2
3
4
5
IP 20
Frame
M1
Frame
M1
Frame
M2
Frame
M2
Frame
M3
Frame
M3
Output current
Continuous (3x380-440 V) [A]
1.2
2.2
3.7
5.3
7.2
9.0
Intermittent (3x380-440 V) [A]
1.8
3.3
5.6
8.0
10.8
13.7
Continuous (3x440-480 V) [A]
1.1
2.1
3.4
4.8
6.3
8.2
Intermittent (3x440-480 V) [A]
1.7
3.2
5.1
7.2
9.5
12.3
Max. cable size:
(mains, motor) [mm
2
/ AWG]
4/10
Max. input current
Continuous (3x380-440 V) [A]
1.9
3.5
5.9
8.5
11.5
14.4
Intermittent (3x380-440 V) [A]
2.6
4.7
8.7
12.6
16.8
20.2
Continuous (3x440-480 V) [A]
1.7
3.0
5.1
7.3
9.9
12.4
Intermittent (3x440-480 V) [A]
2.3
4.0
7.5
10.8
14.4
17.5
Max. mains fuses [A]
See
6.6 Fuses
Environment
Estimated power loss [W], Best case/
Typical
1)
18.5/
25.5
28.5/
43.5
41.5/
56.5
57.5/
81.5
75.0/
101.6
98.5/
133.5
Weight enclosure IP20 [kg]
1.1
1.1
1.6
1.6
3.0
3.0
Efficiency [%], Best case/Typical
1)
96.8/
95.5
97.4/
96.0
98.0/
97.2
97.9/
97.1
98.0/
97.2
98.0/
97.3
Table 9.3 Mains Supply 3x380-480 V AC
1)
At rated load conditions.
Normal overload 150% or 1 min
Frequency converter
Typical Shaft Output [kW]
P5K5
5.5
P7K5
7.5
P11K
11
P15K
15
P18K
18.5
P22K
22
Typical Shaft Output [HP]
7.5
10
15
20
25
30
IP 20
Frame
M3
Frame
M3
Frame
M4
Frame
M4
Frame
M5
Frame
M5
Output current
Continuous (3x380-440 V) [A]
12.0
15.5
23.0
31.0
37.0
42.0
Intermittent (3x380-440 V) [A]
18.0
23.5
34.5
46.5
55.5
63.0
Continuous (3x440-480 V) [A]
11.0
14.0
21.0
27.0
34.0
40.0
Intermittent (3x440-480 V) [A]
16.5
21.3
31.5
40.5
51.0
60.0
Max. cable size:
(mains, motor) [mm
2
/AWG]
4/10
16/6
Max. input current
Continuous (3x380-440 V) [A]
19.2
24.8
33.0
42.0
34.7
41.2
Intermittent (3x380-440 V) [A]
27.4
36.3
47.5
60.0
49.0
57.6
Continuous (3x440-480 V) [A]
16.6
21.4
29.0
36.0
31.5
37.5
Intermittent (3x440-480 V) [A]
23.6
30.1
41.0
52.0
44.0
53.0
Max. mains fuses [A]
See
6.6 Fuses
Environment
Estimated power loss [W], Best case/
Typical
1)
131.0/
166.8
175.0/
217.5
290.0/
342.0
387.0/
454.0
395.0/
428.0
467.0/
520.0
Weight enclosure IP20 [kg]
3.0
3.0
Efficiency [%], Best case/Typical
1)
98.0/
97.5
98.0/
97.5
97.8/
97.4
97.7/
97.4
98.1/
98.0
98.1/
97.9
Table 9.4 Mains Supply 3x380-480 V AC
1)
At rated load conditions.
Specifications
VLT
®
Micro Drive FC 51 Design Guide
90
MG02K202 - VLT
®
is a registered Danfoss trademark
9