3-03 Maximum Reference
Range:
Function:
Maximum Reference is adjustable in the
range Minimum Reference -4999.
50.00
*
[-4999-4999] Enter value for Maximum Reference.
The sum of all internal and external
references are clamped (limited) to the
maximum reference value,
3-03 Maximum
Reference
.
3-41 Ramp1 Ramp-up Time
Range:
Function:
Size
related
*
[0.05-3600.00 s] Enter ramp-up time from 0 Hz to
rated motor frequency (f
M,N
) set
in
1-23 Motor Frequency
.
Choose a ramp-up time ensuring
that torque limit is not exceeded,
see
4-16 Torque Limit in Motor
Mode
.
3-42 Ramp1 Ramp-down Time
Range:
Function:
Size
related
*
[0.05-3600.00
s]
Enter ramp down time from rated
motor frequency (f
M,N
) in
1-23
Motor Frequency
to 0 Hz.
Choose a ramp down time that
does not cause over-voltage in
inverter due to regenerative
operation of motor. Furthermore,
regenerative torque must not
exceed limit set in
4-17 Torque
Limit in Generator Mode
.
7.4.2 Quick Menu Parameters - PI Basic
Settings QM2
The following is a brief description of the parameters for
the PI Basic Settings. For a more detailed description, see
VLT
®
Micro Drive Programming Guide
, MG02C.
1-00 Configuration Mode
Option:
Function:
Use this parameter for selecting the
application control principle to be used when
a Remote Reference is active.
NOTE
Changing this parameter will reset
3-00
Reference Range
,
3-02 Minimum Reference
and
3-03 Maximum Reference
to their
default values.
NOTE
This parameter cannot be adjusted
while motor runs.
[0 ]
*
Speed
Open Loop
For normal speed control (References).
1-00 Configuration Mode
Option:
Function:
[3]
Process
Closed
Loop
Enables process closed loop control. See
parameter group
7-3* Process PI Control
for
further information on PI-controller.
3-02 Minimum Reference
Range:
Function:
0.00
*
[-4999-4999] Enter value for minimum reference.
The sum of all internal and external
references are clamped (limited) to the
minimum reference value,
3-02 Minimum
Reference
.
3-03 Maximum Reference
Range:
Function:
Maximum Reference is adjustable in the
range Minimum Reference -4999.
50.00
*
[-4999-4999] Enter value for Maximum Reference.
The sum of all internal and external
references are clamped (limited) to the
maximum reference value,
3-03 Maximum
Reference
.
3-10 Preset Reference
Option:
Function:
Each parameter set-up contains 8 preset
references which are selectable via 3
digital inputs or bus.
[18]
Bit2
[17]
Bit1
[16]
Bit0
[16]
Bit0
0
0
0
0
0
0
1
1
0
1
0
2
0
1
1
3
1
0
0
4
1
0
1
5
1
1
0
6
1
1
1
7
Table 7.1 Parameter Group 5-1* Digital
Inputs Option [16], [17] and [18]
[0.00]
*
-100.00-100.00% Enter the different preset references
using array programming.
Normally, 100%=value set in
3-03
Maximum Reference
.
However, there are exceptions if
3-00
Reference Range
is set to
[0] Min - Max
.
Example 1:
3-02 Minimum Reference
is set to 20 and
3-03 Maximum Reference
is set to 50. In
this case 0%=0 and 100%=50.
Example 2:
Programming
VLT
®
Micro Drive FC 51 Design Guide
66
MG02K202 - VLT
®
is a registered Danfoss trademark
7