than 1 second again with change saving or press [Back]
without change saving. Press [Back] to leave the
parameter.
7.8 Initialise the Frequency Converter to
Default Settings in two Ways
7.8.1 Initialise the Frequency Converter to
Default Settings in two Ways
Recommended initialisation (via
14-22 Operation Mode
)
1.
Select
14-22 Operation Mode
.
2.
Press [Ok].
3.
Select
Initialisation
and Press [Ok].
4.
Cut off the mains supply and wait until the
display turns off.
5.
Reconnect the mains supply - the frequency
converter is now reset.
Except the following
parameters.
8-30 Protocol
8-31 Address
8-32 Baud Rate
8-33 Parity / Stop Bits
8-35 Minimum Response Delay
8-36 Maximum Response Delay
15-00 Operating Hours to
15-05 Over Volt's
15-03 Power Up's
15-04 Over Temp's
15-05 Over Volt's
15-30 Alarm Log: Error Code
15-4* Drive identification parameters
Two finger initialization:
1.
Power off the frequency converter.
2.
Press [Ok] and [Menu].
3.
Power up the frequency converter while still
pressing the keys above for 10 sec.
4.
The frequency converter is now reset, except the
following parameters:
15-00 Operating Hours
15-03 Power Up's
15-04 Over Temp's
15-05 Over Volt's
15-4* Drive identification parameters
Initialisation of parameters is confirmed by AL80 in the
display after the power cycle.
Programming
VLT
®
Micro Drive FC 51 Design Guide
MG02K202 - VLT
®
is a registered Danfoss trademark
69
7
7
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]