10.7 Fuse Replacement in Decentral Access Module (DAM 510)
If a single fuse blows, replace all the fuses with fuses from the same batch (fuse CAT number 5012006.25, SIBA).
Procedure
Remove the screws [1] and remove the cover.
1
e30bg800.10
Illustration 61: Opening the Cover on DAM 510
Use a screwdriver to remove the fuses and replace them with the same number of identical type fuses.
e30bg801.10
Illustration 62: Removing the Fuse
Replace the cover and tighten the screws. The tightening torque is 2 Nm.