No & Name
Range
Default
Function
0.1–999.0 s
999.0 s
Enter the process controller integral time.
Obtain quick control through a short integral
time, though if the integral time is too short,
the process becomes unstable. An excessively
long integral time disables the integral action.
Table 2.5
Motor Set-up
The Quick Menu Motor Set-up guides you through the
needed motor parameters.
No & Name
Range
Default
Function
[0] Interna-
tional
[1] US
0
0-06 GridType [0] -[132]
please see
start-up wizard
for open-loop
application
Size selected Select operating
mode for restart
upon
reconnection of
the drive to AC
line voltage after
power-down
1-10 Motor
Construction
*[0] Motor
construction
[1] PM, non-
salient SPM
[0]
Asynchron
0.12–110 kW/
0.16–150 hp
Size related
Enter motor
power from
nameplate data
50.0–1,000.0 V Size related
Enter motor
voltage from
nameplate data
20.0–400.0 Hz
Size related
Enter motor
frequency from
nameplate data
0.01–10,000.00
A
Size related
Enter motor
current from
nameplate data
100.0–9,999.0
RPM
Size related
Enter motor
nominal speed
from nameplate
data
No & Name
Range
Default
Function
0.1–1,000.0
Size related
This parameter is
available only
when 1-10 Motor
Construction
Design is set to
[1] PM, non-
salient SPM
.
NOTE!
Changing this
parameter will
affect settings
of other
parameters
1-30 Stator
Resistance (Rs)
0.000–99.990
Size related
Set the stator
resistance value
1-37 d-axis
Inductance
(Ld)
0–1000
Size related
Enter the value
of the d-axis
inductance.
Obtain the value
from the
permanent
magnet motor
data sheet. The
de-axis
inductance
cannot be found
by performing an
AMA.
1-39 Motor
Poles
2-100
4
Enter the number
of motor poles
1-40 Back EMF
at 1000 RPM
10–9,000
Size related
Line-Line RMS
back EMF voltage
at 1000 RPM
1-73 Flying
Start
[0] Disabled
[1] Enabled
0
Select Enable to
enable the
Adjustable
frequency drive
to catch a
spinning motor
How to Program
VLT
®
HVAC Basic Drive Programming Guide
2-10
MG18B222 - VLT
®
is a registered Danfoss trademark
2