5-53 Term. 29 High Ref./Feedb. Value
Range:
Function:
Size
related
*
[-999999.999 -
999999.999
ReferenceFeed-
backUnit]
Enter the high reference value
[RPM] for the motor shaft
speed and the high feedback
value, see also
5-58 Term. 33
High Ref./Feedb. Value
. Select
terminal 29 as a digital input
(
5-02 Terminal 29 Mode
=
[0]
input
(default) and
5-13 Terminal 29 Digital Input
=
applicable value).
This parameter is available for
only.
3.6.6 5-9* Bus Controlled
This parameter group selects digital and relay outputs via
a serial communication bus setting.
5-90 Digital & Relay Bus Control
Range:
Function:
0
*
[0 - 0xFFFFFFFF ] This parameter holds the state of the
digital outputs and relays that is
controlled by bus.
A logical '1' indicates that the output is
high or active.
A logical '0' indicates that the output is
low or inactive.
Bit 0 - 3
Reserved
Bit 4
Relay 1 output terminal
Bit 5
Relay 2 output terminal
Bit 6 - 23
Reserved
Bit 24
Terminal 42 Digital Output
Bit 25
Terminal 45 Digital Output
Bit 26 - 31
Reserved
Table 3.7
Parameters
VLT
®
HVAC Basic Drive Programming Guide
3-30
MG18B222 - VLT
®
is a registered Danfoss trademark
3