No & Name
Range
Default
Function
50.0–1,000.0 V
Size related
Enter motor voltage from nameplate data
20.0–400.0 Hz
Size related
Enter motor frequency from nameplate data
0.01–10,000.00 A
Size related
Enter motor current from nameplate data
100.0–9,999.0 RPM
Size related
Enter motor nominal speed from nameplate data
0.1–1,000.0
Size related
This parameter is available only when 1-10 Motor
Construction Design is set to
[1] PM, non-salient
SPM
.
NOTE!
Changing this parameter will affect settings
of other parameters
1-29 Automatic Motor
Adaption (AMA)
See
Off
Performing an AMA optimizes motor performance.
1-30 Stator Resistance
(Rs)
0.000–99.990
Size related
Set the stator resistance value
1-37 d-axis Inductance
(Ld)
0–1000
Size related
Enter the value of the d-axis inductance.
Obtain the value from the permanent magnet
motor data sheet. The de-axis inductance cannot
be found by performing an AMA.
1-39 Motor Poles
2-100
4
Enter the number of motor poles
1-40 Back EMF at 1000
RPM
10–9,000
Size related
Line-Line RMS back EMF voltage at 1000 RPM
1-73 Flying Start
When PM is selected, Flying Start is enabled and
cannot disable
1-73 Flying Start
[0] Disabled
[1] Enabled
0
Select
[1] Enable
to enable the drive to catch a
motor spinning due to line drop-out. Select
[0]
Disable
if this function is not required. When is
enabled
and
1-72 Start Function
have no function. is active in VVC+ mode only.
3-02 Minimum Reference -4,999-4,999
0
The minimum reference is the lowest value
obtainable by summing all references.
3-03 Maximum Reference -4,999–4,999
50
The maximum reference is the lowest obtainable
by summing all references.
0.05–3,600.0 s
Size related
Ramp-up time from 0 to rated 1-23 Motor
Frequency if Asynchron motor is selected; ramp-up
time from 0 to 1-25 Motor Nominal Speed if PM
motor is selected
0.05–3,600.0 s
Size related
Ramp-down time from rated 1-23 Motor
Frequency to 0 if Asynchron motor is selected;
ramp-down time from 1-25 Motor Nominal Speed
to 0 if PM motor is selected
4-12 Motor Speed Low
Limit [Hz]
0.0–400 Hz
0 Hz
Enter the minimum limit for low speed
4-14 Motor Speed High
Limit [Hz]
0.0–400 Hz
65 Hz
Enter the maximum limit for high speed
4-19 Max Output
Frequency
0–400
Size related
Enter the maximum output frequency value
5-40 Function Relay [0]
Function relay
See 5-40 Function Relay
Alarm
Select the function to control output relay 1.
5-40 Function Relay [1]
Function relay
See 5-40 Function Relay
Drive running
Select the function to control output relay 2.
How to Program
VLT
®
HVAC Basic Drive Programming Guide
MG18B222 - VLT
®
is a registered Danfoss trademark
2-5
2
2