CAUTION
If the Drive Bypass Function is
enabled, the adjustable frequency
drives are no longer Safety Certified
(for using the Safe Stop in versions
where included).
The setting options below are all related to the Cascade
Controller.
Wiring diagrams and settings for parameter, see parameter
group 25-** for more details.
[200] Full
Capacity
All pumps running and at full speed
[201] Pump1
Running
One or more of the pumps controlled by the
Cascade Controller are running. The function
will also depend on the setting of in
25-06 Number Of Pumps
. If set to
[0] No,
Pump
1 refers to the pump controlled by relay
RELAY1, etc. If set to
[1] Yes,
Pump 1 refers to
the pump controlled by the adjustable
frequency drive only (without any of the built-
in relays involved) and Pump 2 to the pump
controlled by the relay RELAY1. See
:
[202] Pump2
Running
See [201]
[203] Pump3
Running
See [201]
Setting in parameter
group 5-3*
Setting in
25-06 Number Of Pumps
[0] No
[1] Yes
[200] Pump 1
Running
Controlled by
RELAY1
Adjustable
Frequency Drive
controlled
[201] Pump 2
Running
Controlled by
RELAY2
Controlled by
RELAY1
[203] Pump 3
Running
Controlled by
RELAY3
Controlled by
RELAY2
Table 3.6
5-30 Terminal 27 Digital Output
Option:
Function:
[0]
*
No operation Same options and functions as parameter
group 5-3*.
5-31 Terminal 29 Digital Output
Option:
Function:
[0]
*
No operation Same options and functions as parameter
group 5-3*.
5-33 Term X30/7 Digi Out (MCB 101)
Option:
Function:
[0]
*
No operation This parameter is active when option module
MCB 101 is mounted in the adjustable
frequency drive. Same options and functions
as parameter group 5-3*.
5-34 On delay, Terminal 42 Digital Output
Range:
Function:
0.01s
*
[0.00–600.00s]
5-35 Off delay, Terminal 42 Digital Output
Range:
Function:
0.01 s
*
[0.00–600.00 s]
3.6.4 5-4* Relays
Parameters for configuring the timing and the output
functions for the relays.
5-40 Function Relay
Array (Relay 1 [0], Relay 2 [1])
Select options to define the function of the relays.
The selection of each mechanical relay is realized in an array
parameter.
Option:
Function:
[0]
No operation
Default for both relays
[1]
Control Ready
The control board receives supply
voltage.
[2]
Drive ready
The adjustable frequency drive is ready
for operation and applies supply the
signal on the control board.
[3]
Drive ready/
remote control
The adjustable frequency drive is ready
for operation in Auto On mode.
[4]
Standby / no
warning
The adjustable frequency drive is ready
for operation. No start or stop
command is given. No warnings are
present.
[5]
Drive running
Motor is running.
[6]
Running / no
warning
Motor runs, and no warning are present.
[7]
Run in range/no
warning
Motor runs within programmed current
ranges, see
and
. No
warnings are present.
[8]
Run on ref/no
warning
Motor runs at reference speed and with
no warnings.
[9]
Alarm
An alarm activates output.
[10]
Alarm or
warning
An alarm or warning activates output.
Parameters
VLT
®
HVAC Basic Drive Programming Guide
3-26
MG18B222 - VLT
®
is a registered Danfoss trademark