5-40 Function Relay
Array (Relay 1 [0], Relay 2 [1])
Select options to define the function of the relays.
The selection of each mechanical relay is realized in an array
parameter.
Option:
Function:
[80]
SL digital output
A
See
. The input
will go high whenever the Smart Logic
Action [38]
Set dig. out. A
high is
executed. The input will go low
whenever the Smart Logic
[32] Action
Set dig. out.
A low is executed.
[81]
SL digital output
B
See
. The input
will go high whenever the Smart Logic
Action [39]
Set dig. out. Bhigh
is
executed. The input will go low
whenever the Smart Logic
[33] Action
Set dig. out. B low
is executed.
[82]
SL digital output
C
See
. The input
will go high whenever the Smart Logic
Action [40]
Set dig. out. C high
is
executed. The input will go low
whenever the Smart Logic
[34] Action
Set dig. out. C low
is executed.
[83]
SL digital output
D
See
. The input
will go high whenever the Smart Logic
[41] Action Set dig. out. D
high is
executed. The input will go low
whenever the Smart Logic
[35] Action
Set dig. out. D low
is executed.
[160] No alarm
The output is high when no alarm is
present.
[161] Running reverse
The output is high when the adjustable
frequency drive is running counter-
clockwise (the logical product of the
status bits ‘running’ AND ‘reverse’).
[165] Local ref. active
The output is high when
3-13 Reference
Site
=
[2] Local
or when
3-13 Reference
Site
=
[0] Linked to hand auto
at the
same time as the LCP is in [Hand on]
mode.
[166] Remote ref.
active
The output is high when
3-13 Reference
Site
[1] or Linked to hand/auto [0]
while
the LCP is in [Auto on] mode.
[167] Start command
activ
The output is high when there is an
active Start command (i.e. via digital
input bus connection or [Hand on] or
[Auto on], and no Stop command is
active).
5-40 Function Relay
Array (Relay 1 [0], Relay 2 [1])
Select options to define the function of the relays.
The selection of each mechanical relay is realized in an array
parameter.
Option:
Function:
[168] Drive in hand
mode
The output is high when the adjustable
frequency drive is in Hand on mode (as
indicated by the LED light above [Hand
on]).
[169] Drive in auto
mode
The output is high when the adjustable
frequency drive is in Hand on mode (as
indicated by the LED light above [Auto
on]).
[193] Sleep Mode
The adjustable frequency drive/system
has set to sleep mode. See parameter
group22-4*.
[194] Broken Belt
Function
A Broken Belt condition has been
detected. This function must be enabled
in
[196] Fire Mode
The adjustable frequency drive is
operating in Fire Mode. See parameter
group 24-0*
Fire Mode
.
[198] Drive Bypass
To be used as signal for activating an
external electromechanical bypass
switching the motor direct on line.
See 24-1*
Drive Bypass.
5-41 On Delay, Relay
Array [9], (Relay 1 [0], Relay 2 [1], Relay 3 [2], Relay 4 [3], Relay 5
[4], Relay 6 [5], Relay 7 [6], Relay 8 [7], Relay 9 [8])
Range:
Function:
0.01 s
*
[0.01 - 600.00 s] Enter the delay of the relay cut-in
time. Select one of available
mechanical relays and MCB 105 in an
array function. See
5-40 Function Relay
.
Relay 3-6 are included in MCB 113.
Parameters
VLT
®
HVAC Basic Drive Programming Guide
3-28
MG18B222 - VLT
®
is a registered Danfoss trademark
3
3