Closed-loop Set-up Wizard
No & Name
Range
Default
Function
[0] International
[1] US
0
[0] -[[132] please see start-up
wizard for open-loop
application
Size selected
Select operating mode for restart upon
reconnection of the adjustable frequency
drive to AC line voltage after power-down.
[0] Open-loop
[3] Closed-loop
0
Change this parameter to Closed-loop
1-10 Motor Construction
*[0] Motor construction
[1] PM, non-salient SPM
[0] Asynchron
Setting the parameter value might change
these parameters:
1-01 Motor Control Principle
1-03 Torque Characteristics
1-14 Damping Gain
1-15 Low Speed Filter Time Const.
1-16 High Speed Filter Time Const.
1-17 Voltage filter time const.
1-20 Motor Power [kW]
1-22 Motor Voltage
1-23 Motor Frequency
1-25 Motor Nominal Speed
1-26 Motor Cont. Rated Torque
1-30 Stator Resistance (Rs)
1-33 Stator Leakage Reactance (X1)
1-35 Main Reactance (Xh)
1-37 d-axis Inductance (Ld)
1-39 Motor Poles
1-40 Back EMF at 1000 RPM
1-66 Min. Current at Low Speed
1-72 Start Function
1-73 Flying Start
4-19 Max Output Frequency
4-58 Missing Motor Phase Function
0.125–150 hp [0.09–110 kW]
Size related
Enter motor power from nameplate data
50.0–1,000.0 V
Size related
Enter motor voltage from nameplate data
20.0–400.0 Hz
Size related
Enter motor frequency from nameplate data
0.0–10,000.00 A
Size related
Enter motor current from nameplate data
100.0–9,999.0 RPM
Size related
Enter motor nominal speed from nameplate
data
0.1–1,000.0
Size related
This parameter is available only when
1-10 Motor Construction Design is set to
[1]
PM, non-salient SPM
.
NOTE!
Changing this parameter will affect
settings of other parameters
1-29 Automatic Motor Adaption
(AMA)
Off
Performing an AMA optimizes motor
performance.
1-30 Stator Resistance (Rs)
0.000–99.990
Size related
Set the stator resistance value
1-37 d-axis Inductance (Ld)
0–1000
Size related
Enter the value of the d-axis inductance.
Obtain the value from the permanent magnet
motor data sheet. The de-axis inductance
cannot be found by performing an AMA.
How to Program
VLT
®
HVAC Basic Drive Programming Guide
2-8
MG18B222 - VLT
®
is a registered Danfoss trademark
2
2