3 Parameters
3.1 Main Menu - Operation and Display -
Group 0
Parameters related to the fundamental functions of the
adjustable frequency drive, function of the LCP buttons
and configuration of the LCP display.
3.1.1 0-0* Basic Settings
0-01 Language
Option:
Function:
Defines the language to be used in the display.
[0]
English
[1]
Deutsch
[2]
Francais
[3]
Dansk
[4]
Spanish
[5]
Italiano
[28]
Bras.port
[255] No Text
0-03 Regional Settings
Option:
Function:
This parameter cannot be adjusted while the
motor is running. In order to meet the needs
for different default settings in different parts of
the world,
is implemented
in the adjustable frequency drive. The selected
setting influences the default setting of the
motor nominal frequency.
[0] Interna-
tional
Sets default value of
[50
Hz].
[1] North
America
Sets the default value of
to 60 Hz.
0-04 Operating State at Power-up
Option:
Function:
Select the operating mode upon reconnection of
the adjustable frequency drive to AC line voltage
after power-down when operating in Hand (local)
mode.
[0] Resume
Resumes operation of the adjustable frequency
drive maintaining the same local reference and
the same start/stop condition (applied by [Hand
On]/[Off] on the LCP or Hand Start via a digital
0-04 Operating State at Power-up
Option:
Function:
input as before the adjustable frequency drive
was powered down).
[1] Forced
stop,
ref=old
Uses saved reference [1] to stop the adjustable
frequency drive but at the same time retains the
local speed reference in memory prior to power-
down. After AC line voltage is reconnected and
after receiving a start command (using the LCP
[Hand On] button or Hand Start command via a
digital input) the adjustable frequency drive
restarts and operates at the retained speed
reference.
0-06 GridType
Option:
Function:
Select the grid type of the supply
voltage/frequency.
NOTE!
Not all choices are supported in
all power sizes.
The IT grid is a line power source
where there are no connections to
ground.
Delta is a line power source where
the secondary part of the
transformer is delta connected and
one phase is connected to ground.
[0]
200-240V/50Hz/IT-grid
[1]
200-240V/50Hz/Delta
[2]
200-240V/50Hz
[10]
380-440V/50Hz/IT-grid
[11]
380-440V/50Hz/Delta
[12]
380-440V/50Hz
[20]
440-480V/50Hz/IT-grid
[21]
440-480V/50Hz/Delta
[22]
440-480V/50Hz
[30]
525-600V/50Hz/IT-grid
[31]
525-600V/50Hz/Delta
[32]
525-600V/50Hz
[100] 200-240V/60Hz/IT-grid
[101] 200-240V/60Hz/Delta
[102] 200-240V/60Hz
[110] 380-440V/60Hz/IT-grid
[111] 380-440V/60Hz/Delta
[112] 380-440V/60Hz