4.
Remove the RFI filter and unplug the RFI cable
from MK100 on the printed circuit board
assembly.
Reinstall in reverse order of this procedure and tighten
hardware according to
7.3.5.3 Fuses and RFI
1.
Remove electrical fuses by removing six nuts (0.5
in [13 mm]), one at each end of each fuse.
2.
Remove three nuts (0.4 in [10 mm]) at the top of
the RFI filter, one per phase.
3.
Remove four mounting screws (T20 thread-
cutting) connecting the RFI filter to the side
channels of the adjustable frequency drive.
4.
Remove the RFI filter and unplug the RFI cable
from MK100 on the printed circuit board
assembly.
Reinstall in reverse order of this procedure and tighten
hardware according to
7.3.5.4 No Options
1.
Remove three nuts (0.4 in [10 mm]) at the top of
the bus bars, one per phase.
2.
Remove six nuts (0.5 in [13 mm]) at the bottom
of the bus bars, two per phase.
3.
Remove the bus bars.
Reinstall in reverse order of this procedure and tighten
hardware according to
7.3.6 Line Power Input Terminal Block
See
1.
Disconnect the customer input power wiring.
2.
Remove input terminals
3.
Remove the two screws (T25) at the bottom of
the terminal block.
4.
Remove the terminal by sliding it down to
disengage it from the metal clips holding it in
place.
Reinstall in reverse order of this procedure and tighten
hardware according to
.
2
3
4
5
6
7
8
9
10
11
130BX464.11
1
12
13
Figure 7.4 Power Terminals
1
Input terminal mounting
block
8
T20 screw
2
U output bus bar bolt (not
shown)
9
T25 screw
3
Output bus bar support
screw (T25)
10
Molex connector
4
Terminal screw
11
Mixing fan
5
Motor terminal mounting
block
12
Output terminal block
retaining screws (T25)
6
Current sensor
13
Input terminal block
retaining screws (T25)
7
Power terminal mounting
plate
Table 7.4 Legend to
Disassembly and Assembly In...
Service Manual
94
Danfoss A/S © Rev. 2014-02-10 All rights reserved.
MG94A222
7
7