3.
Remove the one standoff (0.3 in [8 mm]) from the
corner of the card.
4.
Remove three nuts (0.3 in [8 mm]).
5.
Remove one screw (T20).
NOTICE!
The screw and one of the nuts also hold in place the (+)
DC and (-) DC wire harness.
Reinstall in reverse order of` this procedure and tighten
hardware according to
NOTICE!
Note the wire cable connections on the (+) UDC and (-)
UDC terminals.
7.4.14 IGBT Gate Drive Card
1
2
3
4
5
6
7
9
8
10
11
13
12
130BX454.10
Figure 7.17 IGBT Gate Drive Card
1
MK1802
8
MK501
2
Inrush card
9
MK601
3
T20 screw
10
MK102
4
T20 screw
11
MK101
5
Gate drive card
12
T20 screw
6
MK701
13
MK1800
7
MK100
Table 7.17 Legend to
1.
Remove the AC input bus bars or RFI option (not
shown) in accordance with the procedure.
2.
(Brake option only) Unplug MK201.
3.
Unplug connections:
•
MK100
•
MK501
•
MK601
•
MK701
•
MK102
4.
Remove six screws (T20 thread-forming).
Reinstall in reverse order of this procedure and tighten
hardware according to
.
7.4.15 Inrush Card
1.
Remove the power card mounting plate in
accordance with
2.
Unplug MK1802.
3.
Remove two screws (T20 thread-forming).
4.
Remove three screws (T20).
Reinstall in reverse order of this procedure and tighten
hardware according to
.
Disassembly and Assembly In...
Service Manual
108
Danfoss A/S © Rev. 2014-02-10 All rights reserved.
MG94A222
7
7
Summary of Contents for VLT FC 103
Page 2: ......