2.3 Status Messages
When the adjustable frequency drive is in status mode,
status messages are generated automatically and appear in
the bottom line of the display (see
).
Status
799RPM 7.83A 36.4kW
0.000
53.2%
1(1)
Auto
Hand
Off
Remote
Local
Ramping
Stop
Running
Jogging
.
.
.
Stand by
130BB037.11
1
2
3
Figure 2.13 Status Display
1 Operation Mode (see
)
2 Reference Site (see
)
3 Operation Status (see
)
Table 2.1 Legend to
2.4 Status Message Definitions
to
define the meaning of the displayed
status messages.
Off
The adjustable frequency drive does not react
to any control signal until [Auto On] or [Hand
On] is pressed.
Auto On
The adjustable frequency drive is controlled
from the control terminals and/or the serial
communication.
The adjustable frequency drive can be
controlled by the navigation keys on the LCP.
Stop commands, reset, reversing, DC brake,
and other signals applied to the control
terminals can override local control.
Table 2.2 Operation Mode
Remote
The speed reference is given from external
signals, serial communication, or internal
preset references.
Local
The adjustable frequency drive uses [Hand On]
control or reference values from the LCP.
Table 2.3 Reference Site
AC Brake
AC Brake was selected in
2-10 Brake Function
.
The AC brake overmagnetizes the motor to
achieve a controlled slow-down.
AMA finish OK
Automatic motor adaptation (AMA) was
carried out successfully.
AMA ready
AMA is ready to start. Press [Hand On] to start.
AMA running
AMA process is in progress.
Braking
The brake chopper is in operation. Generative
energy is absorbed by the brake resistor.
Braking max.
The brake chopper is in operation. The power
limit for the brake resistor defined in
2-12 Brake Power Limit (kW)
has been reached.
Coast
•
Coast inverse was selected as a function
for a digital input (parameter group
5-1*
Digital Inputs
). The corresponding terminal
is not connected.
•
Coast activated by serial communication.
Ctrl. Ramp-down Control Ramp-down was selected in
14-10 Mains Failure
.
•
The AC line voltage is below the value set
in
14-11 Mains Voltage at Mains Fault
at
line power fault.
•
The adjustable frequency drive ramps
down the motor using a controlled ramp-
down.
Current High
The adjustable frequency drive output current
is above the limit set in
4-51 Warning Current
High
.
Current Low
The adjustable frequency drive output current
is below the limit set in
4-52 Warning Speed
Low
.
DC Hold
DC Hold is selected in
1-80 Function at Stop
and a stop command is active. The motor is
held by a DC current set in
2-00 DC Hold/
Preheat Current
.
DC Stop
The motor is held with a DC current (
2-01 DC
Brake Current
) for a specified time (
2-02 DC
Braking Time
).
•
DC Brake is activated in
2-03 DC Brake Cut-
in Speed [RPM]
and a Stop command is
active.
•
DC Brake (inverse) is selected as a function
for a digital input (parameter group
5-1*
Digital Inputs
). The corresponding terminal
is not active.
•
The DC Brake is activated via serial
communication.
Feedback high
The sum of all active feedbacks is above the
feedback limit set in
4-57 Warning Feedback
High
.
Operator Interface and Adju...
Service Manual
26
Danfoss A/S © Rev. 2014-02-10 All rights reserved.
MG94A222
2
2