FC 102, FC 202, and FC 103
N110
N132
N160
N200
N250
N315
High/Normal Load*
NO
NO
NO
NO
NO
NO
Typical Shaft output at 400 V [kW]
110
132
160
200
250
315
Typical Shaft output at 460 V [hp]
150
200
250
300
350
450
Typical Shaft Output at 480 V [kW]
132
160
200
250
315
355
Enclosure IP21
D1h
D1h
D1h
D2h
D2h
D2h
Enclosure IP54
D1h
D1h
D1h
D2h
D2h
D2h
D3h
D3h
D3h
D4h
D4h
D4h
Output current
Continuous (at 400 V) [A]
212
260
315
395
480
588
Intermittent (60 s overload) (at 400 V) [A]
233
286
347
435
528
647
Continuous (at 460/500 V) [A]
190
240
302
361
443
535
Intermittent (60 s overload) (at 460/500 V)
[kVA]
209
264
332
397
487
588
Continuous kVA (at 400 V) [kVA]
147
180
218
274
333
407
Continuous kVA (at 460 V) [kVA]
151
191
241
288
353
426
Max. input current
Continuous (at 400 V) [A]
204
251
304
381
381
463
463
567
Continuous (at 460/500 V) [A]
183
231
291
348
348
427
427
516
Max. cable size: line power, motor, brake
and load share [mm
2
] (AWG
2)
)
5)
2x95
(2x3/0)
2x185
(2x350)
Max. external electrical fuses [A]
1)
315
350
400
550
630
800
Estimated power loss at 400 V [W]
4)
2555
2949
3764
4109
5129
6663
Estimated power loss at 460 V [W]
2257
2719
3622
3561
4558
5703
Weight, enclosure IP21, IP54 kg (lbs)
62 (135)
125 (275)
Weight, enclosure IP20 kg (lbs)
62 (135)
125 (275)
Efficiency
4)
0.98
Output frequency
0–800 Hz
0–600 Hz
*Normal overload = 110% current for 60 s
Table 1.12 Line Power Supply 3x380–480 V AC
1) For type of fuse, see the Instruction Manual.
2) American Wire Gauge
3) Measured using 16.5 ft [5 m] shielded motor cables at rated load and rated frequency.
4) The typical power loss is at nominal load conditions and within ± 15% (depending on various voltage and cable
conditions).
5) Field wiring terminals on FC 102 N132, N160, and N315 models are not intended to receive conductors one size
larger.
Values are based on a typical motor efficiency (eff2/eff3 border line). Motors with lower efficiency add to the
power loss in the adjustable frequency drive and those with higher efficiency decrease it.
The losses are based on the default switching frequency. The losses increase significantly at higher switching
frequencies. LCP and typical control card power consumption values are included. Further options and customer
load may add up to 30 W to the losses. (Though typically, only 4 W extra for a fully loaded control card, or options
for slot A or slot B, each).
Introduction
Service Manual
14
Danfoss A/S © Rev. 2014-02-10 All rights reserved.
MG94A222