Bottom section
This always shows the state of the adjustable frequency
drive in Status mode.
Top section
Middle section
Bottom section
Status
43 RPM
1.4 Hz
Auto Remote Running
! Pwr.card temp (W29)
2.9%
5.44 A
25.3 kW
1(1)
130BP074.10
!
Figure 2.5
Indicator lights (LEDs)
If certain threshold values are exceeded, the alarm and/or
warning LED lights up. A status and alarm text appears on
the control panel.
The On LED is activated when the adjustable frequency
drive receives power from the AC line voltage, a DC bus
terminal, or an external 24 V supply. At the same time, the
back light is on.
•
Green LED/On: Control section is working.
•
Yellow LED/Warn.: Indicates a warning.
•
Flashing Red LED/Alarm: Indicates an alarm.
On
Warn.
Alarm
130BP044.10
Figure 2.6 LCP Keys
Menu keys
The menu keys are divided into functions. The keys below
the display and LEDs are used for parameter set-up,
including choice of display indication during normal
operation.
130BP045.10
Status
Quick
Menu
Main
Menu
Alarm
Log
Figure 2.7 Menu Keys
[Status]
Indicates the status of the adjustable frequency drive
and/or the motor. Three different readouts can be chosen
by pressing the [Status] key:
5 line readouts, 4 line readouts, or Smart Logic Control.
Use
[Status]
to select the mode of display or change back
to Display mode from Quick Menu mode, Main Menu
mode, or Alarm mode. Press [Status] to toggle between
the three readouts.
[Quick Menu]
Allows quick set-up of the adjustable frequency drive. The
most common functions can be programmed here.
The [Quick Menu] consists of:
-
My Personal Menu
-
Quick Set-up
-
Function Set-up
-
Changes Made
-
Loggings
The Function set-up provides quick and easy access to all
parameters required for most applications. Among other
features, it also includes parameters for selecting which
variables to display on the LCP.
[Main Menu]
Is used for programming all parameters. The Main Menu
parameters can be accessed immediately unless a
password has been created via
0-60 Main Menu Password
,
0-61 Access to Main Menu w/o Password
,
0-65 Quick Menu
Password
, or
0-66 Access to Quick Menu w/o Password
.
[Alarm Log]
Displays an Alarm list of the five latest alarms (numbered
A1-A5). To obtain more details about an alarm, press the
navigation keys to find the alarm number and press [OK].
Information is displayed about the condition of the
adjustable frequency drive before it enters alarm mode.
The [Alarm log] key on the LCP allows access to both the
Alarm log and Maintenance log.
[Back]
Reverts to the previous step or layer in the navigation
structure.
Back
Figure 2.8 Back Icon
Operator Interface and Adju...
Service Manual
MG94A222
Danfoss A/S © Rev. 2014-02-10 All rights reserved.
23
2
2
Summary of Contents for VLT FC 103
Page 2: ......