1.9 Power-dependent Specifications
FC 302
N90K
N110
N132
N160
N200
N250
High/Normal Load*
HO
NO
HO
NO
HO
NO
HO
NO
HO
NO
HO
NO
Typical Shaft output at 400 V [kW]
90
110
110
132
132
160
160
200
200
250
250
315
Typical Shaft output at 460 V [hp]
125
150
150
200
200
250
250
300
300
350
350
450
Typical Shaft Output at 500 V [kW]
110
132
132
160
160
200
200
250
250
315
315
355
Enclosure IP21
D1h
D1h
D1h
D2h
D2h
D2h
Enclosure IP54
D1h
D1h
D1h
D2h
D2h
D2h
Enclosure IP20
D3h
D3h
D3h
D4h
D4h
D4h
Output current
Continuous (at 400 V) [A]
177
212
212
260
260
315
315
395
395
480
480
588
Intermittent (60 s overload) (at 400 V) [A]
266
233
318
286
390
347
473
435
593
528
720
647
Continuous (at 460/500 V) [A]
160
190
190
240
240
302
302
361
361
443
443
535
Intermittent (60 s overload) (at 460/500 V)
[kVA]
240
209
285
264
360
332
453
397
542
487
665
588
Continuous kVA (at 400 V) [kVA]
123
147
147
180
180
218
218
274
274
333
333
407
Continuous kVA (at 460 V) [kVA]
127
151
151
191
191
241
241
288
288
353
353
426
Continuous kVA (at 500 V) [kVA]
139
165
165
208
208
262
262
313
313
384
384
463
Max. input current
Continuous (at 400 V) [A]
171
204
204
251
251
304
304
381
381
463
463
567
Continuous (at 460/500 V) [A]
154
183
183
231
231
291
291
348
348
427
427
516
Max. cable size: line power, motor, brake
and load share [mm
2
(AWG
2)
)]
5)
2x95
(2x3/0)
2x185
(2x350 mcm)
Max. external electrical fuses [A]
1
315
350
400
550
630
800
Estimated power loss at 400 V [W]
4
2031
2559
2289
2954
2923
3770
3093
4116
4039
5137
5005
6674
Estimated power loss at 460 V [W]
1828
2261
2051
2724
2089
3628
2872
3569
3575
4566
4458
5714
Weight, enclosure IP21, IP54 kg (lbs)
62 (135)
125 (275)
Weight, enclosure IP20 kg (lbs)
62 (135)
125 (275)
Efficiency
4)
0.98
Output frequency
0–800 Hz
0–600 Hz
*High overload = 150% current for 60 s, Normal overload = 110% current for 60 s
Table 1.11 Line Power Supply 3x380–500 V AC