380–480 V/380–500 V units
525–690 V units
Inrush Circuit Enabled [V DC]
370
550
Inrush Circuit Disabled [V DC]
395
570
Inverter Undervoltage Disable [V DC]
373
553
Undervoltage Warning [V DC]
410
585
Inverter Undervoltage Re-enable
(warning reset) [V DC]
413
602
380–480 V units
380–500 V units
Overvoltage Warning (without brake) [V DC]
778
817
1084
Dynamic Brake Turn On [V DC]
778
810
1099
Inverter Overvoltage Re-Enable (warning reset)
[V DC]
786
821
1099
Overvoltage Warning (with brake) [V DC]
810
828
1109
Overvoltage Trip [V DC]
820
855
1130
Table 1.19 DC Voltage Levels