Below are a list of the actual status words (far right on display) and what they mean
Operation Status
AC Brake
AC-Brake was selected in par. 2-10 Brake Function. The motor is slowed down via the active down
ramp and feeds the FC with generative energy. The AC Brake over-magnetizes the motor to achieve
a controlled end of the active ramp.
AMA finish OK
Enable complete or reduced AMA was selected in par. 1-29 Automatic Motor Adaptation (AMA).
The Automatic Motor Adaptation was carried out successfully.
AMA ready
Enable complete or reduced AMA was selected in par. 1-29 Automatic Motor Adaptation (AMA).
The Automatic Motor Adaptation is ready to start. Press [Hand On] on the LCP to start.
AMA running
Enable complete or reduced AMA was selected in par. 1-29 Automatic Motor Adaptation (AMA).
The AMA process is in progress.
Braking
The brake chopper is in operation. Generative energy is absorbed by the Brake resistor.
Braking max.
The brake chopper is in operation. The power limit for the brake resistor defined in par.
2-12 Brake Power Limit (kW) is reached.
Bus Jog 1
PROFIDrive profile was selected in par. 8-10 Control Word Profile. Via serial communication the
Jog 1 function is activated. The Motor is running with par. 8-90 Bus Jog 1 Speed.