Start delay
In par. 1-71 Start Delay, the delay of the starting time was set. A Start command was activated
and the delay time is still running. The Motor will start after the delay time has expired.
Start fwd/rev
Enable start forward and Enable start reverse were selected as functions for two different digital
inputs (parameter group 5-1*). To start the motor a direction dependent start signal has to be
given and the corresponding terminal has to be active.
Start inhibit
PROFIDrive profile was selected in par. 8-10 Control Word Profile. The start inhibition is active.
The FC needs the first part (e.g. 0x047E) of the two-part start command via serial communication
to allow starting. See also operation status control ready.
Stop
[Off] was pressed on the LCP or Stop inverse was selected as a function for a digital input (Group
5-1*). The corresponding terminal is not active.
Trip
An alarm occurred. It is possible, provided the cause of the alarm is cleared, to reset the alarm
via a Reset signal ([Reset]-Key on the LCP, a control terminal or serial communication).
Trip lock
A serious alarm occurred. It is possible, provided the cause of the alarm was cleared, to reset the
alarm after the mains have been switched off and on again. This can be done via a reset signal
([Reset] on the LCP, a control terminal or serial communication).
Unit/Drive not ready
PROFIDrive profile was selected in par. 8-10 Control Word Profile. A Control word is sent to the
FC via serial communication with Off 1, Off 2 and Off 3 active. Start inhibit is active. To enable
Start, see operation status Start inhibit
.