consumption by the solenoid bridge in the PVED must be reduced or to remove a steering control
conflict between the OSP and the PVED.
The default value disables this functionality i.e. the magnetic valve bridge is enabled at all times.
Generally, the magnetic valve bridge is enabled when the PVED-CL receives a non-zero flow request.
Symbol
Index
Default
Value range
Magnetic valves off delay time
115
30 000
1 to 30 000 (ms)
If Qm is set to 0, then the magnetic valve bridge will be disabled immediately when the SASA sensor is
the selected device.
Operation Manual
PVED-CL Controller for Electro-Hydraulic Steering, Version 1.38
Steering by Steering Wheel – Open Loop
©
Danfoss | May 2016
11025583 | AQ00000216en-US0302 | 51