VLT 5000 series
FC 302 series
Parameter 360 Term. 45, Output
max. scale
6-62 Terminal X30/8 Max.
Scale
Range
0 – 500%
0 – 200%
Table 5.126 Conversion of Parameter 360
VLT 5000 series
FC 302 series
Parameter
361 Encoder loss threshold
Not converted
Range
0 – 600%
Table 5.127 Conversion of Parameter 361
5.5 VLT
®
5000 Parameter Group 4
VLT 5000 series
FC 302 series
Parameter 400 Brake function/
over voltage cont.
2-10 Brake Function
2-17 Over-voltage Control
Options
[0] Off
[0] Off
[1] Resistor brake
Par. 2-10 = *1* Resistor brake
Par. 2-17 = [0] Off
[2] Over voltage
control
Par. 2-10 = [0] Off
Par. 2-17 = [2] Enabled
[3] Over voltage
control and stop
Par- 2-10 = [0] Off
Par. 2-17 = [1] Enabled (not at
stop)
Table 5.128 Conversion of Parameter 400
VLT 5000 series
FC 302 series
Parameter 401 Brake resistor, [
Ω
]
30-81 Brake Resistor (ohm)
Options
Power unit dependable Power unit dependable
Table 5.129 Conversion of Parameter 401
VLT 5000 series
FC 302 series
Parameter 402 Brake power limit,
[kW]
2-12 Brake Power Limit
(kW)
Range
Depends on unit
Depends on unit
Table 5.130 Conversion of Parameter 402
VLT 5000 series
FC 302 series
Parameter 403 Power monitoring 2-13 Brake Power Monitoring
Options
[0] Off
[0] Off
[1] Warning
[1] Warning
[2] Trip
[2] Trip
Table 5.131 Conversion of Parameter 403
VLT 5000 series
FC 302 series
Parameter
404 Brake check
2-15 Brake Check
Options
[0] Off
[0] Off
[1] Warning
[1] Warning
[2] Trip
[2] Trip
Table 5.132 Conversion of Parameter 404
Parameter Mapping Lists
Operating Instructions
30
Danfoss A/S © Rev. 2014-03-06 All rights reserved.
MG37E102