VLT 5000 series
FC 302 series
Parameter 229 Frequency bypass,
bandwidth
Stored in EEprom only
Range
0 - 100%
Table 5.81 Conversion of Parameter 229
VLT 5000 series
FC 302 series
Parameter 230 Frequency Bypass
1
4-61 Bypass Speed From [Hz]
4-63 Bypass Speed To [Hz]
Range
0 – par. 200
0 – par. 4-14
Table 5.82 Conversion of Parameter 230
VLT 5000 series
FC 302 series
Parameter 2-31 Frequency Bypass
2
4-61 Bypass Speed From [Hz]
4-63 Bypass Speed To [Hz]
Range
0 – par. 200
0 – par. 4-14
Table 5.83 Conversion of Parameter 231
VLT 5000 series
FC 302 series
Parameter 232 Frequency Bypass
3
4-61 Bypass Speed From [Hz]
4-63 Bypass Speed To [Hz]
Range
0 – par. 200
0 – par. 4-14
Table 5.84 Conversion of Parameter 232
VLT 5000 series
FC 302 series
Parameter 233 Frequency Bypass
4
4-61 Bypass Speed From [Hz]
4-63 Bypass Speed To [Hz]
Range
0 – par. 200
0 – par. 4-14
Table 5.85 Conversion of Parameter 233
VLT 5000 series
FC 302 series
Parameter 234 Motor phase
monitor
4-58 Missing Motor Phase
Function
Range
[0] Enable
[2] Trip 1000 ms
[1] Disable
[0] Disable
Table 5.86 Conversion of Parameter 234
5.4 VLT
®
5000 Parameter Group 3
VLT 5000 series
FC 302 series
Parameter 300 Terminal 16, input
5-16 Terminal X30/2 Digital
Input
Options
[0] No function
[0] No function
[1] Reset
[1] Reset
[2] Stop inverse
[6] Stop inverse
[3] Only start clockwise,
on
[12] Enable start forward
[4] Jog
[14] Jog
[5] Preset reference, on [15] Preset reference, on
[6] Preset reference, lsb [16] Preset reference bit 0
[7] Freeze reference
[17] Freeze reference
[8] Freeze output
[20] Freeze output
[9] Speed up
[21] Speed up
[10] Choice of setup, lsb [23] Setup select bit 0
[11] Catch-up
[28] Catch-up
[12] Ramp 2
[34] Ramp bit 0
[13] Mains failure
inverted
Not supported
[29] Data change lock
Not supported
Comments FC 302 does not have a digital input 16, so this is
linked to
5-16 Terminal X30/2 Digital Input
Table 5.87 Conversion of Parameter 300
VLT 5000 series
FC 302 series
Parameter 301 Terminal 17, input
5-17 Terminal X30/3
Digital Input
Options
[0] No function
[0] No operation
[1] Reset
[1] Reset
[2] Stop inverse
[6] Stop inverse
[3] Only start
anticlockwise, on
[13] Enable start reverse
[4] Jog
[14] Jog
[5] Preset reference, on
[15] Preset reference, on
[6] Preset reference, msb
[17] Preset reference bit
1
[7] Freeze reference
[19] Freeze reference
[8] Freeze output
[20] Freeze output
[9] Speed down
[22] Speed down
[10] Choice of setup, msb [24] Setup select bit 1
[11] Slow down
[29] Slow down
[12] Ramp 2
[34] Ramp bit 0
[13] Mains failure inverted Not supported
[23] Pulse reference
[32] Pulse input
[24] Safety interlock
Not supported
[29] Data change lock
Not supported
Comments FC 302 does not have a digital input 17, so this is
linked to
5-16 Terminal X30/2 Digital Input
Table 5.88 Conversion of Parameter 301
Parameter Mapping Lists
Operating Instructions
22
Danfoss A/S © Rev. 2014-03-06 All rights reserved.
MG37E102