VLT 5000 series
FC 302 series
Parameter
number
009
0-09 Performance Monitor
Parameter
number
010
0-10 Active Set-up
Parameter
number
011
0-11 Programming Set-up
Parameter
number
012
0-12 This Set-up Linked to
Options
[12] DC link voltage
[V]
[1630] DC link voltage [V]
[13] Thermal load,
motor [%]
[1618] Thermal load, motor
[%]
[14] Thermal load,
VLT® [%]
[1635] Inverter thermal [%]
[15] Running hours
[hours]
[1501] Running hours [hours]
[16] Digital input
[1660] Digital input
[17] Analogue input
53 [V]
[1662] Analogue input 53 [V]
[18] Analogue input
54 [V]
[1664] Analogue input 54 [V]
[19] Analogue input
60 [mA]
[1662] Analogue input 53
[mA]
[20] Pulse reference
[Hz]
[1651] Pulse reference [Hz]
[21] Ext. reference
[%]
[1650] Ext. reference [%]
[22] Status word
[hex]
[1603] Status word [hex]
[23] Brake effect/2
min [kW]
[1633] Brake effect/2 min
[kW]
[24] Brake effect/sec
[kW]
[1632] Brake effect/sec [kW]
[25] Heat sink temp. [1634] Heat sink temp.
[26] Alarm word
[hex]
[27] Control word
[hex]
[1600] Control word [hex]
[28] Warning word 1
[hex]
[29] Warning word 2
[hex]
[30] Com. Option
warning [hex]
[953] Com. Option warning
[hex]
[31] RPM [min]
[1617] Speed RPM [min]
[32] RPM x scaling
[min]
[1609] Custom readout
[33] LCP display text Not possible
Table 5.10 Conversion of Parameters 009 to 012
VLT 5000 series
FC 302 series
Parameter
013 Local Ctrl./config
Not converted
Table 5.11 Conversion of Parameter 013
VLT 5000 series
FC 302 series
Parameter
014 Local Stop key
0-41 [Off] Key on LCP
Options
[0] Disable
[0] Disable
[1] Enable
[1] Enable
[2] Password
Table 5.12 Conversion of Parameter 014
VLT 5000 series
FC 302 series
Parameter
015 Local Jogging
Not converted
Options
[0] Disable
[1] Enable
Table 5.13 Conversion of Parameter 015
VLT 5000 series
FC 302 series
Parameter
016 Local Reversing
Not converted
Options
[0] Disable
[1] Enable
Table 5.14 Conversion of Parameter 016
VLT 5000 series
FC 302 series
Parameter
017 Local Stop key
0-43 [Reset] Key on LCP
Options
[0] Disable
[0] Disable
[1] Enable
[1] Enable
[2] Password
Table 5.15 Conversion of Parameter 017
VLT 5000 series
FC 302 series
Parameter 018 Lock for data
change
0-61 Access to Main Menu
w/o Password
Options
[0] Not locked
[0] Full access
[1] Lock
[1] LCP: Read only
Table 5.16 Conversion of Parameter 018
VLT 5000 series
FC 302 series
Parameter 019 Power-Up Mode
0-04 Operating State at
Power-up
Options
[0] Auto Restart, use
saved ref.
[0] Resume
[1] Forced stop, use
saved ref.
[1] Forced stop, use saved
ref.
[2] Forced stop, set ref
= 0.
[2] Forced stop, set ref = 0
Table 5.17 Conversion of Parameter 019
Parameter Mapping Lists
Operating Instructions
MG37E102
Danfoss A/S © Rev. 2014-03-06 All rights reserved.
15