WARNING
Touching the electrical parts may be fatal - even after
the equipment has been disconnected from mains.
Voltage [V]
Minimum waiting time (minutes)
4
15
200-240
0.25-3.7 kW
5.5-37 kW
380-480
0.25-7.5 kW
11-75 kW
525-600
0.75-7.5 kW
11-75 kW
525-690
11-75 kW
High voltage may be present even when the warning LED
indicator lights are off.
Table 2.1 Discharge Time
Also make sure that other voltage inputs have been
disconnected, such as external 24 V DC, load sharing
(linkage of DC intermediate circuit), as well as the motor
connection for kinetic back-up.