VLT 5000 series
FC 302 series
Parameter 127 DC brake cut-in
frequency
2-04 DC Brake Cut In
Speed [Hz]
Range
0.0 (Off) – f
max
(par. 202)
0.0 (Off) – f
max
(par. 414)
Table 5.46 Conversion of Parameter 127
VLT 5000 series
FC 302 series
Parameter 128 Motor thermal
protection
1-90 Motor Thermal
Protection
Options
[0] No protection
[0] No protection
[1] Thermistor warning
[1] Thermistor warning
[2] Thermistor trip
[2] Thermistor trip
[3] ETR warning 1
[3] ETR warning 1
[4] ETR trip 1
[4] ETR trip 1
[5] ETR warning 2
[5] ETR warning 2
[6] ETR trip 2
[6] ETR trip 2
[7] ETR warning 3
[7] ETR warning 3
[8] ETR trip 3
[8] ETR trip 3
[9] ETR warning 4
[9] ETR warning 4
[10] ETR trip 4
[10] ETR trip 4
Table 5.47 Conversion of Parameter 128
VLT 5000 series
FC 302 series
Parameter 129 External motor fan
1-91 Motor External Fan
Options
[0] No
[0] No
[1] Yes
[1] Yes
Table 5.48 Conversion of Parameter 129
VLT 5000 series
FC 302 series
Parameter 130 Start frequency
1-75 Start Speed [Hz]
Range
0.0 – 10.0 Hz
0.0 – 500 Hz P.U depending
Table 5.49 Conversion of Parameter 130
VLT 5000 series
FC 302 series
Parameter
131 Initial voltage
Not converted
Table 5.50 Conversion of Parameter 131
VLT 5000 series
FC 302 series
Parameter
145 Minimum DC brake time
Not converted
Table 5.51 Conversion of Parameter 132
5.3 VLT
®
5000 Parameter Group 2
VLT 5000 series
FC 302 series
Parameter 200 Output Frequency Range/
Direction
4-10 Motor Speed
Direction
Options
[0] Only clockwise, 0 – 132 Hz
[0] Clockwise
[1] Both directions, 0 – 132 Hz
[2] Both directions
[2] Only clockwise, 0 – 1000 Hz
[0] Clockwise
[3] Both directions, 0 – 1000 Hz [2] Both directions
[4] Only counter clockwise, 0 –
132 Hz
[1] Counter
clockwise
[5] Only counter clockwise, 0 –
1000 Hz
[1] Counter
clockwise
Table 5.52 Conversion of Parameter 200
VLT 5000 series
FC 302 series
Parameter 201 Output frequency
low limit
4-12 Motor Speed Low
Limit [Hz]
Range
0.0 – par. 202 F
max
0 – par. 414 F
max
[Hz]
Table 5.53 Conversion of Parameter 201
VLT 5000 series
FC 302 series
Parameter 202 Output frequency
high limit
4-14 Motor Speed High
Limit [Hz]
4-19 Max Output Frequency
Range
0.0 – 132/1000 Hz
0 – 1000 Hz
Table 5.54 Conversion of Parameter 202
VLT 5000 series
FC 302 series
Parameter 203 Reference/feedback area 3-00 Reference Range
Options
[0] Min – Max
[0] Min – Max
[1] - Max - +Max
[1] - Max - +Max
Table 5.55 Conversion of Parameter 203
VLT 5000 series
FC 302 series
Parameter
204 Minimum
reference
3-02 Minimum
Reference
Range
-100,000.000 – par.
205 Ref
max
-100,000.000 – par.
3-03 Ref
max
Table 5.56 Conversion of Parameter 204
Parameter Mapping Lists
Operating Instructions
MG37E102
Danfoss A/S © Rev. 2014-03-06 All rights reserved.
19
5