3 Installation
3.1 Connecting the Bus Line
Terminate the bus line at both ends of each segment. A
mismatch of impedance may result in reflections on the
line resulting in corrupt data transmission.
The DeviceNet Option Card contains a suitable termination.
To activate the termination, turn on
Switch 1
on the
DeviceNet converter option. By default, the switch is
turned off.
NOTICE
Notice that pin numbers are colour-coded on the
DeviceNet connector.
Unlike the VLT
®
5000, the FC 302 DeviceNet connectors
are colour-coded to avoid swapping the bus wires.
130BD826.10
5
4
2
3
1
+24V
GND
Drain
CAN_L
CAN_H
Illustration 3.1 Connecting Wires to VLT DeviceNet Converter
MCA 194
Pin no.
Terminal
Colour
Name
1
V-
Black
GND
2
CAN_L
Blue
CAN LOW
3
Drain
(bare)
Screen
4
CAN_H
White
CAN HIGH
5
V+
Red
+24 V
Table 3.1 Correct Colour-Coding
3.2 Mechanical Installation
3.2.1 Mount the Option
130B
T318.11
Illustration 3.2 Installing Fieldbus Option
Installation
Operating Instructions
8
Danfoss A/S © Rev. 2014-03-06 All rights reserved.
MG37E102
3
3