VLT 5000 series
FC 302 series
Parameter 319 Terminal 42,
Output
Digital = Par. 5-32 DO X30/7
(MCB 101)
Analogue values= Par. 6-50
AO 42
Pulse = Par. 5-66 DO X30/6
Parameter 321 Terminal 45,
Output
Digital = Par. 5-33 DO X30/7
(MCB 101)
Analogue values= Par. 6-60
AO X30/8
Pulse = Par. 5-66 DO X30/6
Options
[60] 0 – SyncRPM
⇒
0
– 20 mA
Not supported
[61] 0 – SyncRPM
⇒
4
– 20 mA
Not supported
[62] 0 – SyncRPM
⇒
0
– 32000 p
Not supported
[63] RPM at F max
⇒
0
– 20 mA
Par. 6-50 = [107] Speed
related to norm 0 - 20 mA
[64] RPM at F max
⇒
4
– 20 mA
Par. 6-50 = [137] Speed
related to norm 4 - 20 mA
[65] RPM at F max
⇒
0
– 32000 p
Par. 5-66 = [107] Speed
related to norm 0 – 32000p
Par. 5-68 = 32000
Table 5.110 Conversion of Parameters 319 to 321
VLT 5000 series
FC 302 series
Parameter 320 Terminal 42 Output,
pulse scaling
5-68 Pulse Output Max
Freq #X30/6
Range
1 – 32000 Hz
0 – 32000 Hz
Table 5.111 Conversion of Parameter 320
VLT 5000 series
FC 302 series
Parameter 322 Terminal 45 Output,
pulse scaling
5-68 Pulse Output Max
Freq #X30/6
Range
1 – 32000 Hz
0– 32000 Hz
Table 5.112 Conversion of Parameter 322
VLT 5000 series
FC 302 series
Parameter 323, 326
5-40 Function Relay
Range
01 Relay
04 Relay
Relay 1
Relay 2
[0] No function
Par. 5-40 = [0] No operation
[1] Control Ready
Par. 5-40 = [1] Control Ready
[2] Ready signal
Par. 5-40 = [2] Drive ready
[3] Ready - Remote
Control
Par. 5-40 = [3] Drive rdy/rem ctrl
[4] Enabled, no
warning
Par. 5-40 = [4] Enable / no
warning
[5] Running
Par. 5-40 = [5] VLT running
[6] Running, no
Warning
Par. 5-40 = [6] Running / no
warning
[7] Running within
range, no warning
Par. 5-40 = [7] Run in range/no
warn
[8] Run at
reference, no
Warning
Par. 5-40 = [8] Run on ref/no
warn
[9] Alarm
Par. 5-40 = [9] Alarm
[10] Alarm or
Warning
Par. 5-40 = [10] Alarm or
Warning
[11] Torque limit
Par. 5-40 = [11] At torque limit
[12] Out of current
range
Par. 5-40 = [12] Out of current
range
[13] Above I low
Par. 5-40 = [13] Below current,
low
1)
[14] Under I high
Par. 5-40 = [14] Above current,
high
1)
[15] Out of
frequency range
Par. 5-40 = [15] Out of speed
range
[16] Over f low
Par. 5-40 = [16] Below speed
low
1)
[17] Under f high
Par.5-40 = [17] Above speed
high
1)
[18] Out of
feedback range
Par. 5-40 = [18] Out of feedb.
Range
[19] Over feedback
low
Par. 5-40 = [16] Below feedback
low
1)
[20] Under
feedback high
Par. 5-40 = [17] Above feedback
high
1)
[21] Thermal
warning
Par. 5-40 = [21] Thermal
warning
Table 5.113 Conversion of Parameters 323 to 326
Parameter Mapping Lists
Operating Instructions
28